A proportional-integral (PI) law based variable speed technology for temperature control in indirect evaporative cooling system

被引:28
作者
Chen, Yi [1 ]
Yan, Huaxia [1 ]
Luo, Yimo [2 ]
Yang, Hongxing [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Peoples R China
[2] Technol & Higher Educ Inst Hong Kong, Fac Sci & Technol, Hong Kong, Peoples R China
关键词
Indirect evaporative cooler; Variable speed; PI control; Energy consumption; Economic analysis; AIR-CONDITIONING SYSTEM; FUZZY-LOGIC CONTROLLER; PERFORMANCE; COOLERS; MODEL; HEAT;
D O I
10.1016/j.apenergy.2019.113390
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The operation of indirect evaporative cooler (IEC) largely depends on the ambient temperature and humidity. To maintain stable indoor temperature, proper controller is essential. On-off control is a mature and stable control method used on constant speed fans. However, large fluctuation of indoor temperature can be observed because of limited control precision. To achieve better thermal comfort, a proportional-integral (PI) law based variable speed technology is proposed for accurate temperature control in an IEC system. This technology had been proved highly effective in central air-conditioning systems and direct expansion air-conditioners in terms of control precision and energy saving, but its techno-economic feasibility in IEC has not been investigated. In this study, annual dynamic simulation has been conducted to an IEC system based on the IEC model and control algorithm. Results show that indoor temperature can be controlled within +/- 0.5 degrees C around the setting point for 81.9% of time, while it is only 30.5% under on-off control. The PI based controller is well adapted to cooling loads in all seasons with good control precision, fast response speed and small overshoots. Response time of PI control is only 10 min in a disturbance rejection test, which is much shorter than 30 min under the on-off control. Annually, IEC with variable speed fans consume 50.0% less energy than that of on-off fans. At last, economic analysis shows that this technology is economically feasible only when the power of primary air fan is larger than 1.75 kW.
引用
收藏
页数:10
相关论文
共 36 条
[1]  
[Anonymous], COMMUNICATION
[2]  
[Anonymous], 6 INT C EN EFF MOT D
[3]  
[Anonymous], BUILD ENV
[4]   Assessments of variable-speed equipment for packaged rooftop units (RTUs) in the United States [J].
Cai, Jie ;
Braun, James E. .
ENERGY AND BUILDINGS, 2018, 164 :203-218
[5]   Comparative study of on-off control and novel high-low control of regenerative indirect evaporative cooler (RIEC) [J].
Chen, Yi ;
Yan, Huaxia ;
Yang, Hongxing .
APPLIED ENERGY, 2018, 225 :233-243
[6]   Investigation on solar assisted liquid desiccant dehumidifier and evaporative cooling system for fresh air treatment [J].
Chen, Yi ;
Yang, Hongxing ;
Luo, Yimo .
ENERGY, 2018, 143 :114-127
[7]   Parameter sensitivity analysis and configuration optimization of indirect evaporative cooler (IEC) considering condensation [J].
Chen, Yi ;
Yang, Hongxing ;
Luo, Yimo .
APPLIED ENERGY, 2017, 194 :440-453
[8]   A simplified analytical model for indirect evaporative cooling considering condensation from fresh air: Development and application [J].
Chen, Yi ;
Luo, Yimo ;
Yang, Hongxing .
ENERGY AND BUILDINGS, 2015, 108 :387-400
[9]   Modeling and experimental study of an indirect evaporative cooler [J].
De Antonellis, Stefano ;
Joppolo, Cesare Maria ;
Liberati, Paolo ;
Milani, Samanta ;
Romano, Francesco .
ENERGY AND BUILDINGS, 2017, 142 :147-157
[10]   Energy saving potential of an indirect evaporative cooler as a pre-cooling unit for mechanical cooling systems in Iran [J].
Delfani, Shahram ;
Esmaeelian, Jafar ;
Pasdarshahri, Hadi ;
Karami, Maryam .
ENERGY AND BUILDINGS, 2010, 42 (11) :2169-2176