Methodology for Determining of Generator Operation Point for Ensuring Voltage Stability Against Generator Faults in Jeju-Haenam HVDC System

被引:6
作者
Kang, Sang-Gyun [2 ]
Seo, Sangsoo [2 ]
Lee, Byongjun [1 ]
Joo, Joon-Young
机构
[1] Korea Univ, Dept Elect Engn, Seoul, South Korea
[2] Korea Univ, Dept Elect & Elect Engn, Seoul, South Korea
关键词
Voltage stability; Current-based HVDC; The Jeju Power System; Generator Contingency; CPF(Continuation Power Flow);
D O I
10.5370/JEET.2010.5.1.054
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a new algorithm for determining generator operation point for maintaining stability considering generator faults in Jeju-Haenam HVDC system. As the HVDC system consumes reactive power for the transmission of active power substantially, compensation of reactive power is essential. And the HVDC system is operated on frequency control mode. That is to say, the HVDC system almost manages system frequency. Therefore, we recognized that the Jeju system could be unstable if the reactive power consumed by the HVDC is insufficient when out-of-step occurs with large generators. When the solution of power flow analysis does not converge due to the unstable system phenomenon, we have difficulty in establishing countermeasures as the post-fault information is not available. In this paper, for the purpose of overcoming this difficulty in establishing countermeasures, we introduce the CPF(Continuation Power Flow) algorithm. This paper suggests an algorithm for calculating the output limitation of the generator to maintain the stability in case of generator fault in the Jeju system.
引用
收藏
页码:54 / 60
页数:7
相关论文
共 16 条
[1]  
Ajjarapu V., COMPUTATIONAL TECHNI
[2]  
AJJARAPU V, 1991, IEEE T
[3]  
CHIANG HD, 1995, IEEE T, V10
[4]  
FLUECK AJ, 2000, IEEE T, V15
[5]  
JANG G, 2005, IEE P GENERATION JUL, P514
[6]  
Koh BE, 2001, ISIE 2001: IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS PROCEEDINGS, VOLS I-III, P1006, DOI 10.1109/ISIE.2001.931612
[7]  
Kundur P, Power System Stability and Control
[8]  
LEE B, 2002, IEEE T, V17
[9]   Novel color-sequential transflective liquid crystal displays [J].
Lee, Ju-Hyun ;
Zhu, Xinyu ;
Wu, Shin-Tson .
JOURNAL OF DISPLAY TECHNOLOGY, 2007, 3 (01) :2-8
[10]   Dynamic analysis of voltage instability in AC-DC systems [J].
Padiyar, KR ;
Rao, SS .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1996, 18 (01) :11-18