Neuro-fuzzy controller of low head hydropower plants using adaptive-network based fuzzy inference system

被引:29
作者
Djukanovic, MB
Calovic, MS
Vesovic, BV
Sobajic, DJ
机构
[1] UNIV BELGRADE,DEPT ELECT ENGN,BELGRADE,YUGOSLAVIA
[2] INST MIHAJLO PUPIN,DEPT AUTOMAT CONTROL,BELGRADE,YUGOSLAVIA
[3] ELECT POWER RES INST,PALO ALTO,CA 94304
关键词
neurofuzzy control; temporal back propagation; ANFIS;
D O I
10.1109/60.638941
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents an attempt of nonlinear, multivariable control of low-head hydropower plants, by using adaptive-network based fuzzy inference system (ANFIS). The new design technique enhances fuzzy controllers with self-learning capability for achieving prescribed control objectives in a near optimal manner. The controller has flexibility for accepting more sensory information, with the main goal to improve the generator unit transients, by adjusting the exciter input, the wicket gate and runner blade positions. The developed ANFIS controller whose control signals are adjusted by using incomplete on-line measurements, can offer better damping effects to generator oscillations over a wide range of operating conditions, than conventional controllers. Digital simulations of hydropower plant equipped with low-head Kaplan turbine are performed and the comparisons of conventional excitation-governor control, state-feedback optimal control and ANFIS based output feedback control are presented. To demonstrate the effectiveness of the proposed control scheme and the robustness of the acquired neuro-fuzzy controller, the controller has been implemented on a complex high-order non-linear hydrogenerator model.
引用
收藏
页码:375 / 381
页数:7
相关论文
共 18 条
[1]  
BERGER KM, 1987, 87139 CWRU
[2]   Neural-net based coordinated stabilizing control for the exciter and governor loops of low head hydropower plants [J].
Djukanovic, M ;
Novicevic, M ;
Dobrijevic, D ;
Babic, B ;
Sobajic, DJ ;
Pao, YH .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1995, 10 (04) :760-767
[3]   NEURAL NET BASED DETERMINATION OF GENERATOR-SHEDDING REQUIREMENTS IN ELECTRIC-POWER SYSTEMS [J].
DJUKANOVIC, M ;
SOBAJIC, DJ ;
PAO, YH .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1992, 139 (05) :427-436
[4]  
DJUKANOVIC M, 1996, 1996 PES SUMM M DENV
[5]   PREDICTION OF POWER-SYSTEM FREQUENCY-RESPONSE AFTER GENERATOR OUTAGES USING NEURAL NETS [J].
DJUKANOVIC, MB ;
POPOVIC, DP ;
SOBAJIC, DJ ;
PAO, YH .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1993, 140 (05) :389-398
[6]   FUZZY-LOGIC POWER-SYSTEM STABILIZER [J].
ELMETWALLY, KA ;
MALIK, OP .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1995, 142 (03) :277-281
[7]  
HANDSCHIN E, 1994, IEEE T POWER SYSTEMS, V6, P533
[8]   ADVANCED PID TYPE FUZZY-LOGIC POWER-SYSTEM STABILIZER [J].
HIYAMA, T ;
KUGIMIYA, M ;
SATOH, H .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1994, 9 (03) :514-520
[9]   TUNING OF POWER-SYSTEM STABILIZERS USING AN ARTIFICIAL NEURAL NETWORK [J].
HSU, YY ;
CHEN, CR .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1991, 6 (04) :612-619
[10]   DESIGN OF FUZZY POWER-SYSTEM STABILIZERS FOR MULTIMACHINE POWER-SYSTEMS [J].
HSU, YY ;
CHENG, CH .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1990, 137 (03) :233-238