Power oscillations damping using wide-area-based solar plant considering adaptive time-delay compensation

被引:17
作者
Abdulrahman, Ismael [1 ]
Belkacemi, Rabie [1 ]
Radman, Ghadir [1 ]
机构
[1] Tennessee Technol Univ, Elect & Comp Engn, Cookeville, TN 38505 USA
来源
ENERGY SYSTEMS-OPTIMIZATION MODELING SIMULATION AND ECONOMIC ASPECTS | 2021年 / 12卷 / 02期
关键词
Inter-area oscillation; Renewable energy; Photovoltaic plant; Wide-area measurements (WAMS); Time delay compensation; Adaptive neuro-fuzzy inference system (ANFIS);
D O I
10.1007/s12667-019-00350-2
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The aim of this paper is to investigate the use of the ever increasing penetration of renewable energy into the power grid to solve challenging problems such as inter area power oscillations without the use of expensive power electronic devices and power system stabilizers. The increase in size of interconnected power systems, energy demand, and installation of remote renewable energies with relatively weak tie-lines has witnessed different stability problems such as low-frequency inter-area oscillations. Inter-area oscillation reduces system stability and transmission capacity. Without effective damping control mechanism, these oscillations could prolong and threaten the security of the system. This paper proposes a supplementary controller from a photovoltaic (PV) solar plant for damping inter-area oscillations. Due to its strong correlation to active power flow and monitoring system stress, area phase-angle difference is employed for the remote signal input of the controller. The signal can be obtained from phasor measurement unit (PMU) through wide-area measurements systems (WAMS). To deal with a wide range of variable delay in the signal input, an adaptive compensator is designed to reduce the impact of the communication latency using neuro-fuzzy inference system. A two-area four-machine test system is used and simulated with a Simulink-based package developed for the work of this study. The time-domain simulations, modal and frequency response analysis demonstrate the capability of the proposed controller to effectively damp inter-area oscillations, under a small- and large-scale disturbances and against a wide range of time delays.
引用
收藏
页码:459 / 489
页数:31
相关论文
共 35 条
  • [1] Abdulrahman I., 2018, SIMULINK BASED PROGR, DOI [10.1109/PESGM.2018.8585773, DOI 10.1109/PESGM.2018.8585773]
  • [2] Wide-Area-Based Adaptive Neuro-Fuzzy SVC Controller for Damping Interarea Oscillations
    Abdulrahman, Ismael
    Radman, Ghadir
    [J]. CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING-REVUE CANADIENNE DE GENIE ELECTRIQUE ET INFORMATIQUE, 2018, 41 (03): : 133 - 144
  • [3] [Anonymous], 2016, Technical reference document: dynamic load modeling
  • [4] [Anonymous], 2014, WECC RENEWABLE ENERG
  • [5] Robust damping of multiple swing modes employing global stabilizing signals with a TCSC
    Chaudhuri, B
    Pal, BC
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2004, 19 (01) : 499 - 506
  • [6] A New Approach to Continuous Latency Compensation With Adaptive Phasor Power Oscillation Damping Controller (POD)
    Chaudhuri, Nilanjan Ray
    Ray, Swakshar
    Majumder, Rajat
    Chaudhuri, Balarko
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2010, 25 (02) : 939 - 946
  • [7] Threshold-Based Monitoring of Multiple Outages With PMU Measurements of Area Angle
    Darvishi, Atena
    Dobson, Ian
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2016, 31 (03) : 2116 - 2124
  • [8] Dorf R., 2011, MODERN CONTROL SYSTE
  • [9] Wide-Area Measurements-Based Two-Level Control Design Considering Signal Transmission Delay
    Dotta, Daniel
    Silva, Aguinaldo S. e
    Decker, Ildemar C.
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2009, 24 (01) : 208 - 216
  • [10] The effective role of AVR and PSS in power systems: Frequency response analysis
    Dudgeon, Graham J. W.
    Leithead, William E.
    Dysko, Adam
    O'Reilly, John
    McDonald, James R.
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (04) : 1986 - 1994