Voltage Sag Forming Method Considering Transient Process

被引:0
作者
Wu, Nan [1 ]
Sun, Jian [1 ]
Chen, Bing [1 ]
Yuan, Xiaodong [1 ]
机构
[1] State Grid Jiangsu Elect Power Co Ltd, Res Inst, Nanjing, Jiangsu, Peoples R China
来源
PROCEEDINGS OF 2018 IEEE 4TH INFORMATION TECHNOLOGY AND MECHATRONICS ENGINEERING CONFERENCE (ITOEC 2018) | 2018年
关键词
voltage sag; transient process; voltage sag generator; short circuit fault;
D O I
暂无
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Voltage sag forming method considering transient process is proposed to simulate voltage sag caused by short circuit fault happened in infinite grid. Voltage after fault is composed of steady and transient component. Steady component can be obtained by symmetrical component method and transient component can be gotten from damping function. Transient component is not only related to circuit parameters, but also related to fault moment. Single phase to ground fault whose impendence is inductive which is the most common in short circuit fault is chosen as the example to analyze steady and transient component of voltage sag. Then the proposed method is testified by simulation.
引用
收藏
页码:1204 / 1208
页数:5
相关论文
共 11 条
[1]  
Chenyu Z., 2018, ELECT POWER ENG TECH, V37, P102
[2]  
Chung Y. H., 2002, IEEE C
[3]  
Kumsuwan Y., 2009, IEEE C
[4]  
Li Dongyu, 2010, IEEE C
[5]  
[吕干云 Lu Ganyun], 2011, [电力系统保护与控制, Power System Protection and Control], V39, P65
[6]  
Ma Yan, 2008, IEEE C
[7]  
Muangjai Worrajak, 2013, IEEE C
[8]  
Oranpiroj K., 2009, IEEE C
[9]  
Zeng Rong, 2010, IEEE C
[10]  
ZHANG Chenyu, 2017, ELECT POWER ENG TECH, V36, P22