High Impedance Fault Detection in EHV Series Compensated Lines Using The Wavelet Transform

被引:0
作者
Eldin, El Sayed Tag [1 ]
Ibrahim, Doaa Khalil [1 ]
Aboul-Zahab, Essam M. [2 ]
Saleh, Saber Mohamed [3 ]
机构
[1] Cairo Univ, Dept Elect Power & Machines, Fac Engn, Cairo, Egypt
[2] Cairo Univ, Dept Elect Power & Machines, Cairo, Egypt
[3] Helwan Univ, Fac Engn, Dept Elect Power & Machines, Cairo, Egypt
来源
2009 IEEE/PES POWER SYSTEMS CONFERENCE AND EXPOSITION, VOLS 1-3 | 2009年
关键词
High impedance fault (HIF); Wavelet transform; series capacitors (SCs); Metal oxide varistors (MOVs); Coupling Capacitor Voltage Transformer (CCVT) and Clarke's Transformation; LOCATION; ALGORITHM;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Coupling capacitive voltage transformers behave as low pass filters which reject the high frequencies associated With voltage signals, so the effect of HIF on voltage signals is neglected. In addition, using series capacitors (SCs) equipped with metal oxide varistors (MOVs) increases the protection relaying problems and complicates the trip decision. This paper presents a high impedance fault detection algorithm for maximum trip time required of 3/4 cycle. The proposed scheme implemented on two different models of HIF in extra high voltage double-ended transmission lines with series capacitors at the middle of the line. The scheme recognizes the distortion of the voltage waveforms caused by the arcs usually associated with HIFs. The discrete wavelet transform (DWT) based analysis, yields three phase voltages in high frequency range which are fed to Clarke's transformation to produce ground and aerial modes voltage components for pattern recognition. The classifier is based on an algorithm that uses recursive method to sum the absolute values of high frequency signals generated over one cycle and shifts one sample. Characteristics of the proposed scheme are fully analyzed by extensive ATP/EMTP simulation studies that clearly reveal that the proposed method can accurately detect HIFs in EHV transmission lines and does not affected by different fault conditions such as fault distance and fault inception angle.
引用
收藏
页码:1550 / +
页数:3
相关论文
共 20 条
[1]   MODELING MOV-PROTECTED SERIES CAPACITORS FOR SHORT-CIRCUIT STUDIES [J].
COURSOL, M ;
NGUYEN, CT ;
LORD, R ;
DO, XD .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (01) :448-453
[2]   A new protection detection technique for high impedance fault using neural network [J].
Eissa, M. M. ;
Sowilam, G. M. A. ;
Sharaf, A. M. .
2006 LARGE ENGINEERING SYSTEMS CONFERENCE ON POWER ENGINEERING, 2006, :146-+
[3]  
ELDIN ET, 2007, P IEEE POW ENG SOC G
[4]   DWT-Based detection and transient power direction-based location of high-impedance faults due to leaning trees in unearthed MV networks [J].
Elkalashy, Nagy I. ;
Lehtonen, Matti ;
Darwish, Hatem A. ;
Taalab, Abdel-Maksoud I. ;
Izzularab, Mohamed A. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (01) :94-101
[5]   Travelling wave based fault location for teed circuits [J].
Evrenosoglu, CY ;
Abur, A .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :1115-1121
[6]  
EVRENOSOGLU CY, 2003, POW TECH C JUN
[7]   Traveling-wave-based fault-location scheme for multiend-aged underground cable system [J].
Gilany, Mahmoud ;
Ibrahim, Doaa Khalil ;
Eldin, El Sayed Tag .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (01) :82-89
[8]   Development of a fuzzy inference system based on genetic algorithm for high-impedance fault detection [J].
Haghifam, M. -R. ;
Sedighi, A. -R. ;
Malik, O. P. .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2006, 153 (03) :359-367
[9]  
KASTENNY B, 2000, 53 ANN C PROT REL EN
[10]   High-impedance fault detection using discrete wavelet transform and frequency range and RMS conversion [J].
Lai, TM ;
Snider, LA ;
Lo, E ;
Sutanto, D .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) :397-407