Organic matter removal in boiler feed water treatment of a power plant with ozone

被引:6
作者
Rico, B [1 ]
Perez, D [1 ]
Lema, JM [1 ]
Lucas, T [1 ]
机构
[1] THERMAL POWER PLANT,AS PONTES,CORUNA,SPAIN
关键词
ozone; power plant boiler feed water; organic matter; trihalomethanes; ozone hydrogen peroxide treatment;
D O I
10.1080/01919512.1997.10382872
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The purpose of this work was to test the effectiveness of ozone as a treatment to remove organic matter of the boiler feed water of a power plant. In the experiments carried out in the power plant Endesa in As Pontes (Spain), chlorine was substituted for ozone in the pre-treatment stage. The use of ozone reduced the organic content of the boiler feed water by an average 20% compared with chlorination and by 50% when ozone was combined with hydrogen peroxide. The latter treatment achieved an organic content in the boiler feed water of less than 40 mu g C/L. The ozone treatment also reduced the content of trihalomethanes in the drinking water, produced by the same plant, to values in the range of 10 mu g/L and even to undetectable values when ozone was combined with hydrogen peroxide, in spite of the postchlorination applied to this stream to ensure a disinfectant capacity though the distribution system.
引用
收藏
页码:471 / 480
页数:10
相关论文
共 7 条
[1]  
GASI TMT, 1990, OZONE-SCI ENG, V13, P179
[2]  
GLAZE W, 1987, ENVIRON SCI TECHNOL, V20, P224
[3]  
RICE RG, 1985, SAFE DRINKING WATER, P123
[4]   WASTE-WATER OZONATION IN THE USA - HISTORY AND CURRENT STATUS - 1989 [J].
ROBSON, CM ;
RICE, RG .
OZONE-SCIENCE & ENGINEERING, 1991, 13 (01) :23-40
[5]   A COMPREHENSIVE INVESTIGATION ON THE APPLICATION OF OZONE IN COOLING WATER-SYSTEMS - CORRELATION OF BENCH-TOP, PILOT SCALE AND FIELD APPLICATION DATA [J].
STRITTMATTER, RJ ;
YANG, B ;
JOHNSON, DA .
OZONE-SCIENCE & ENGINEERING, 1993, 15 (01) :47-80
[6]  
WELLAUER R, 1990, OZONE-SCI ENG, V12, P243
[7]  