Application of automated blind for daylighting in tropical region

被引:50
作者
Chaiwiwatworakul, Pipat [1 ]
Chirarattananon, Surapong [1 ]
Rakkwamsuk, Pattana [2 ]
机构
[1] King Mongkuts Univ Technol Thonburi, Joint Grad Sch Energy & Environm, Div Energy, Bangkok 10140, Thailand
[2] King Mongkuts Univ Technol Thonburi, Sch Energy Environm & Mat, Bangkok 10140, Thailand
关键词
Glare; Luminance; Direct component and internally reflected component of interior illuminance; VENETIAN BLIND; LIGHTING SYSTEM; ILLUMINANCE;
D O I
10.1016/j.enconman.2009.07.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper reports an experimental and simulation study on application of automated Venetian blind for daylighting in tropical climate. A horizontal blind system operating automatically under programmed control was constructed and integrated onto the glazed windows to form a window system with an automated blind in a room of a laboratory building. A dimming controller was also integrated to the lighting system of the room. Different operation schemes of the window system were devised and tested in the attempt to maximize energy savings while maintaining the quality of the visual environment in the room. Intensive measurement of illuminance of the interior space was undertaken during the experiments. A methodology for calculation of interior daylight illuminance and associated glare corresponding to the configurations of the experiments was adopted. The method was coded into a computer program. Results of calculation from the program agree well with those from experiments for all the schemes of operation conducted. The program was used to simulate the situation when each scheme of operation was implemented for a whole year. It was found that such window system with automated blind enabled energy savings of 80%, but a more sophisticated scheme also helped maintain the interior visual quality at high level. (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2927 / 2943
页数:17
相关论文
共 19 条
[1]  
Aizlewood M., 2001, Monitoring procedures for the assessment of daylighting performance of buildings
[2]   A methodology for simulation of daylight room illuminance distribution and light dimming for a room with a controlled shading device [J].
Athienitis, AK ;
Tzempelikos, A .
SOLAR ENERGY, 2002, 72 (04) :271-281
[3]  
BRACKETT W, 1983, 83038 CR NAV CIV ENG
[4]   Evaluation of sky luminance and radiance models using data of north Bangkok [J].
Chaiwiwatworakul, P ;
Chirarattananon, S .
LEUKOS, 2004, 1 (02) :107-126
[5]  
Chauvel P., 1982, LIGHT RES TECHNOL, V14, P31
[6]   Daylighting through light pipes in the tropics [J].
Chirarattananon, S ;
Chedsiri, S ;
Liu, RS .
SOLAR ENERGY, 2000, 69 (04) :331-341
[7]   Daylight availability and models for global and diffuse horizontal illuminance and irradiance for Bangkok [J].
Chirarattananon, S ;
Chaiwiwatworakul, P ;
Pattanasethanon, S .
RENEWABLE ENERGY, 2002, 26 (01) :69-89
[8]   THE EFFECT OF SLAT ANGLE OF WINDOWS WITH VENETIAN BLINDS ON HEATING AND COOLING LOADS OF BUILDINGS IN SOUTH-KOREA [J].
CHO, SH ;
SHIN, KS ;
ZAHEERUDDIN, M .
ENERGY, 1995, 20 (12) :1225-1236
[9]  
CHUNG T, 2005, P 5 LUX PAC SUST LIG
[10]   Impact of window blinds on daylight-linked dimming and automatic on/off lighting controls [J].
Galasiu, AD ;
Atif, MR ;
MacDonald, RA .
SOLAR ENERGY, 2004, 76 (05) :523-544