Deadbands, Droop, and Inertia Impact on Power System Frequency Distribution

被引:53
作者
Vorobev, Petr [1 ]
Greenwood, David M. [2 ]
Bell, John H. [3 ]
Bialek, Janusz W. [1 ]
Taylor, Philip C. [2 ]
Turitsyn, Konstantin [3 ,4 ]
机构
[1] Skolkovo Inst Sci & Technol Skoltech, Moscow 121205, Russia
[2] Newcastle Univ, Sch Elect & Elect Engn, Newcastle Upon Tyne NE1 7RU, Tyne & Wear, England
[3] MIT, Dept Mech Engn, 77 Massachusetts Ave, Cambridge, MA 02139 USA
[4] DE Shaw Grp, New York, NY USA
基金
英国工程与自然科学研究理事会;
关键词
Frequency control; droop control; dead bands; low inertia grids; frequency fluctuations; STABILITY; SERVICES;
D O I
10.1109/TPWRS.2019.2895547
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Power system inertia is falling as more energy is supplied by renewable generators, and there are concerns about the frequency controls required to guarantee satisfactory system performance. The majority of research into the negative effect of low inertia has focused on poor dynamic response following major disturbances, when the transient frequency dip can become unacceptable. However, another important practical concern-keeping average frequency deviations within acceptable limits-was mainly out of the sight of the research community. In this manuscript, we present a method for finding the frequency probability density function (PDF) for a given power system. We pass from an initial stochastic dynamic model to deterministic equations for the frequency PDF, which are analyzed to uncover key system parameters influencing frequency deviations. We show that system inertia has little effect on the frequency PDF, making virtual inertia services insufficient for keeping frequency close to nominal under ambient load fluctuations. We establish that aggregate system droop and deadband width are the only parameters that have major influence on the average frequency deviations, suggesting that energy storage might be an excellent solution for tight frequency regulation. We also show that changing the governor deadband width does not significantly affect generator movement.
引用
收藏
页码:3098 / 3108
页数:11
相关论文
共 42 条
[1]  
Abdur-Rahman I, 2010, POWER ENG-US, V114, P66
[2]  
[Anonymous], 2017, 2017 AUSTRALASIAN U, DOI DOI 10.1109/AUPEC.2017.8282404
[3]  
[Anonymous], PESTR1 IEEE TASK FOR
[4]  
[Anonymous], 2012, Power System Dynamics. Stability and Control
[5]  
[Anonymous], FOKKER PLNACK EQUATI
[6]  
[Anonymous], 1994, POWER SYSTEM STABILI
[7]  
[Anonymous], ENTSO E SUPPORTING D
[8]  
[Anonymous], P 2017 55 ANN ALL C
[9]  
[Anonymous], NATL GRID FREQUENCY
[10]  
[Anonymous], 2011, NERC Balancing and Frequency Control