Direct dry cooling system through hybrid ventilation for improving cooling efficiency in power plants

被引:11
作者
Kong, Yanqiang [1 ]
Wang, Weijia [1 ]
Huang, Xianwei [1 ]
Yang, Lijun [1 ]
Du, Xiaoze [1 ]
Yang, Yongping [1 ]
机构
[1] North China Elect Power Univ, Key Lab Condit Monitoring & Control Power Plant E, Minist Educ, Sch Energy Power & Mech Engn, Beijing 102206, Peoples R China
基金
中国国家自然科学基金;
关键词
Air-cooled condenser; Hybrid ventilation; Ambient wind; Thermo-flow performances; Turbine back pressure; AIR-COOLED CONDENSERS; IMPROVED ENERGY PERFORMANCE; THERMO-FLOW PERFORMANCES; COIL CONFIGURATIONS; HEAT-EXCHANGERS; STEAM CONDENSER; WATER CHILLERS; CFD SIMULATION; AMBIENT WINDS;
D O I
10.1016/j.applthermaleng.2017.03.067
中图分类号
O414.1 [热力学];
学科分类号
摘要
The thermo-flow performances of conventional air-cooled condenser (ACC) using mechanical ventilation are basically susceptible to ambient winds due to its geometrical flaws, so more attentions have been paid to weakening such unfavorable effects, but the hybrid ventilation has never been considered. Based on representative 2 x 600 MW power generating units, two types of hybrid ventilation direct dry cooling systems (HVDDCS) utilizing the buoyancy force from the cooling tower, circular-type and rectangular-type, are developed. Furthermore, the thermo-flow performances in three wind directions of 0, 45 and 90 are presented and compared with the conventional ACCs. The results show that the hot plume recirculation of the peripheral condenser cells for HVDDCS can be avoided, thus the inlet air temperature of air-cooled condensers is reduced. For circular HVDDCS, the reversed flows in upwind condenser cells are much weakened, leading to increased heat rejection and improved cooling performance in any case. In the wind direction of 0, the rectangular HVDDCS shows a superior performance to those in the wind directions of 45 and 90, so it is applicable to the region with a prevailing wind direction. The HVDDCS could be recommended for the potential engineering application thanks to its more energy efficient performance. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:254 / 268
页数:15
相关论文
共 21 条
[1]  
ANSYS Inc, 2015, FLUENT US GUID
[2]   Numerical investigation of fan performance in a forced draft air-cooled steam condenser [J].
Bredell, JR ;
Kröger, DG ;
Thiart, GD .
APPLIED THERMAL ENGINEERING, 2006, 26 (8-9) :846-852
[3]   Achieving near-water-cooled power plant performance with air-cooled condensers [J].
Bustamante, John G. ;
Rattner, Alexander S. ;
Garimella, Srinivas .
APPLIED THERMAL ENGINEERING, 2016, 105 :362-371
[4]   The effect of wind on the optimal design and performance of a modular air-cooled condenser for a concentrated solar power plant [J].
Butler, C. ;
Grimes, R. .
ENERGY, 2014, 68 :886-895
[5]   A novel layout of air-cooled condensers to improve thermo-flow performances [J].
Chen, Lei ;
Yang, Lijun ;
Du, Xiaoze ;
Yang, Yongping .
APPLIED ENERGY, 2016, 165 :244-259
[6]   The influence of wind on the performance of forced draught air-cooled heat exchangers [J].
Duvenhage, K ;
Kroger, DG .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 1996, 62 (2-3) :259-277
[7]   Performance prediction of an improved air-cooled steam condenser with deflector under strong wind [J].
Gao, X. F. ;
Zhang, C. W. ;
Wei, J. J. ;
Yu, B. .
APPLIED THERMAL ENGINEERING, 2010, 30 (17-18) :2663-2669
[8]   A numerical study on the effect of roof windbreak structures in an air-cooled system [J].
Gu, Hongfang ;
Zhe, Zhang ;
Wang, Haijun ;
Qi, Chen .
APPLIED THERMAL ENGINEERING, 2015, 90 :684-693
[9]   Wind tunnel simulation of exhaust recirculation in an air-cooling system at a large power plant [J].
Gu, Zhifu ;
Chen, Xuerei ;
Lubitz, William ;
Li, Yan ;
Luo, Wonlin .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2007, 46 (03) :308-317
[10]  
Heyns J.A., 2008, PERFORMANCE CHARACTE