On the Use of Monopole Antennas for Determining the Effect of the Enclosure of a Power Transformer Tank in Partial Discharges Electromagnetic Propagation

被引:39
作者
Albarracin, Ricardo [1 ]
Alfredo Ardila-Rey, Jorge [2 ]
Mas'ud, Abdullahi Abubakar [3 ]
机构
[1] Boslan Engn & Consulting SA, Generat & Distribut Network Area, Dept Elect Engn, Innovat Technol & R&D, Madrid 28034, Spain
[2] Univ Tecn Federico Santa Maria, Dept Elect Engn, Santiago 8940000, Chile
[3] Jubail Ind Coll, Dept Elect & Elect Engn Technol, Rd 6,8244 Al Huwailat, Al Jubail 35718, Saudi Arabia
来源
SENSORS | 2016年 / 16卷 / 02期
关键词
VHF and UHF sensors; condition monitoring; partial discharges; power transformer tank; monopole antennas; PD MEASUREMENTS; SEPARATION; LOCATION;
D O I
10.3390/s16020148
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
A well-defined condition-monitoring for power transformers is key to implementing a correct condition-based maintenance (CBM). In this regard, partial discharges (PD) measurement and its analysis allows to carry out on-line maintenance following the standards IEC-60270 and IEC-60076. However, new PD measurements techniques, such as acoustics or electromagnetic (EM) acquisitions using ultra-high-frequency (UHF) sensors are being taken into account, IEC-62478. PD measurements with antennas and the effect of their EM propagation in power transformer tanks is an open research topic that is considered in this paper. In this sense, an empty tank model is studied as a rectangular cavity and their resonances are calculated and compared with their measurement with a network analyser. Besides, two low cost improved monopole antennas deployed inside and outside of the tank model capture background noise and PD pulses in three different test objects (Nomex, twisted pair and insulator). The average spectrum of them are compared and can be found that mainly, the antenna frequency response, the frequency content distribution depending on the PD source and the enclosure resonances modes are the main factors to be considered in PD acquisitions with these sensors. Finally, with this set-up, it is possible to measure PD activity inside the tank from outside.
引用
收藏
页数:18
相关论文
共 24 条
  • [1] Separation of sources in radiofrequency measurements of partial discharges using time-power ratio maps
    Albarracin, R.
    Robles, G.
    Martinez-Tarifa, J. M.
    Ardila-Rey, J.
    [J]. ISA TRANSACTIONS, 2015, 58 : 389 - 397
  • [2] [Anonymous], 2016, Antenna Theory and Design
  • [3] [Anonymous], 2012, Advanced Engineering Electromagnetics
  • [4] [Anonymous], 2009, ELECT POWER EQUIPMEN
  • [5] [Anonymous], 2016, IEC62478
  • [6] [Anonymous], 2015, IEC Standard 60270, V3
  • [7] Cheng D.K, 1998, FUNDAMENTALS ELECTRO
  • [8] Sensitivity of UHF PD Measurements in Power Transformers
    Coenen, S.
    Tenbohlen, S.
    Markalous, S. M.
    Strehl, T.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (06) : 1553 - 1558
  • [9] A UHF Technique for Advanced PD Measurements on Inverter-Fed Motors
    Fabiani, Davide
    Cavallini, Andrea
    Montanari, Gian Carlo
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (05) : 2546 - 2556
  • [10] A review on machinery diagnostics and prognostics implementing condition-based maintenance
    Jardine, Andrew K. S.
    Lin, Daming
    Banjevic, Dragan
    [J]. MECHANICAL SYSTEMS AND SIGNAL PROCESSING, 2006, 20 (07) : 1483 - 1510