Oil flooded compression cycle enhancement for two-stage heat pump in cold climate region: System design and theoretical analysis

被引:16
作者
Luo, Baojun [1 ]
机构
[1] Hunan Univ, Coll Mech & Vehicle Engn, Changsha 410082, Hunan, Peoples R China
关键词
Heat pump; Vapor injection; Oil flooding; Flooded compression; Cold climate; R32; SCROLL COMPRESSOR; PERFORMANCE; R410A; OPTIMIZATION; REGENERATION;
D O I
10.1016/j.enconman.2016.02.050
中图分类号
O414.1 [热力学];
学科分类号
摘要
In order to improve the performance of air source heat pump in cold climate region, a combined oil flooded compression with regenerator and vapor injection cycle system is suggested in this paper, which integrates oil flooded compression with regenerator into a conventional vapor injection cycle. A mathematical model is developed and parametric studies on this cycle are conducted to evaluate the benefits of the novel system. The performances of the novel system using R410A and R32 are compared with those of vapor injection cycle system. The improvement of coefficient of performance (COP) can reach up to nearly 9% based on the same isentropic efficiency, while 17.2% based on assumption that there is a 10% rise in isentropic efficiency brought by oil flooded compression cycle. The heating capacity is reduced by 8-18% based on the same volumetric efficiency, while could be less than 10% in a practical system. The discharge temperature is largely decreased and can be below 100 degrees C at -40 degrees C T-e and 50 degrees C T-c condition for R32. The theoretical results demonstrate this novel heat pump has a high potential for improving the performance of air source heat pump in cold climate region. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:52 / 59
页数:8
相关论文
共 19 条
[1]   Testing, simulation and soft-optimization of R410A low-GWP alternatives in heat pump system [J].
Alabdulkarem, Abdullah ;
Eldeeb, Radia ;
Hwang, Yunho ;
Aute, Vikrant ;
Radermacher, Reinhard .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 60 :106-117
[2]   Performance of the coupling of the flat plate collector and a heat pump system associated with a vertical heat exchanger for heating of the two types of greenhouses system [J].
Awani, S. ;
Chargui, R. ;
Kooli, S. ;
Farhat, A. ;
Guizani, A. .
ENERGY CONVERSION AND MANAGEMENT, 2015, 103 :266-275
[3]  
Bahman A. M., 2014, 15 INT REFR AIR COND, P2284
[4]   Experimental testing of an oil-flooded hermetic scroll compressor [J].
Bell, Ian H. ;
Groll, Eckhard A. ;
Braun, James E. ;
Horton, W. Travis .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2013, 36 (07) :1866-1873
[5]   Liquid flooded compression and expansion in scroll machines - Part II: Experimental testing and model validation [J].
Bell, Ian H. ;
Lemort, Vincent ;
Groll, Eckhard A. ;
Braun, James E. ;
King, Galen B. ;
Horton, W. Travis .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (07) :1890-1900
[6]   Performance of vapor compression systems with compressor oil flooding and regeneration [J].
Bell, Ian H. ;
Groll, Eckhard A. ;
Braun, James E. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (01) :225-233
[7]  
Bertsch SS, 2006, INT REFR AIR COND C, P135
[8]   Two-stage air-source heat pump for residential heating and cooling applications in northern US climates [J].
Bertsch, Stefan S. ;
Groll, Eckhard A. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (07) :1282-1292
[9]   An analysis of solar assisted ground source heat pumps in cold climates [J].
Emmi, Giuseppe ;
Zarrella, Angelo ;
De Carli, Michele ;
Galgaro, Antonio .
ENERGY CONVERSION AND MANAGEMENT, 2015, 106 :660-675
[10]  
Hugenroth J., 2006, IHR-IRHACE Conference, P492