A comparative study of frosting behavior on finned tube heat exchanger under different fan control modes

被引:34
作者
Zhang, Long [1 ,2 ,3 ]
Jiang, Yiqiang [1 ,2 ]
Dong, Jiankai [1 ,2 ]
Yao, Yang [1 ,2 ]
Deng, Shiming [3 ]
机构
[1] Harbin Inst Technol, Sch Architecture, Harbin, Heilongjiang, Peoples R China
[2] Minist Ind & Informat Technol, Key Lab Cold Reg Urban & Rural Human Settlement E, Beijing, Peoples R China
[3] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Peoples R China
关键词
Comparative study; Frosting behavior; Fan control mode; Finned tube heat exchanger; THERMAL PERFORMANCE; GROWTH; DESIGN; PREDICTION;
D O I
10.1016/j.applthermaleng.2019.114063
中图分类号
O414.1 [热力学];
学科分类号
摘要
Although a large number of studies have been carried out on investigating the frosting behaviors and its impacts on finned tube heat exchangers (FTHXs), comparative studies for frosting behaviors on FTHXs among using different fan control modes were still lacking. Hence, a related experimental study comparing two different outdoor air fan control modes has been carried out, and the study results are presented in this paper. The study results demonstrated that compared to the constant outdoor air fan speed control mode, the constant air flow rate control mode can make the frost at the exit from leeward fins more compact and uniform, and lead to an accelerated frost growth on the surfaces of fins and tubes but an impeded frost growth on the edge of windward fins. At the end of a 60-min frosting duration, the protruded thickness of frost on the edge of windward fins, and frost thickness at the entrance to the windward fins under the constant air flow rate control mode were 7.9% and 11.1% smaller than those under the constant outdoor air fan speed control mode. In contrast, frost mass on the FTHX and the averaged frost density on the surfaces of fins and tubes under constant air flow rate control mode were 6.7% and 16.7% larger than those under constant outdoor air fan speed control mode. Furthermore, the averaged air side pressure drop, air velocity and total heat transfer rate of the FTHX under the constant air flow rate control mode were 134.5%, 82.4% and 13.4% larger than those under the constant outdoor air fan speed control mode during the 60-min frosting duration.
引用
收藏
页数:9
相关论文
共 37 条
[1]  
Ali D, 1992, EFFECTS FROST FORMAT
[2]  
Coleman H.W., 2018, Experimentation, validation, and uncertainty analysis for engineers
[3]   A new model for predicting performance of fin-and-tube heat exchanger under frost condition [J].
Cui, J. ;
Li, W. Z. ;
Liu, Y. ;
Zhao, Y. S. .
INTERNATIONAL JOURNAL OF HEAT AND FLUID FLOW, 2011, 32 (01) :249-260
[4]   Effect of frost morphology on the thermal-hydraulic performance of fan-supplied tube-fin evaporators [J].
da Silva, Diogo L. ;
Melo, Claudio ;
Hermes, Christian J. L. .
APPLIED THERMAL ENGINEERING, 2017, 111 :1060-1068
[5]   First-principles modeling of frost accumulation on fan-supplied tube-fin evaporators [J].
da Silva, Diogo L. ;
Hermes, Christian J. L. ;
Melo, Claudio .
APPLIED THERMAL ENGINEERING, 2011, 31 (14-15) :2616-2621
[6]   Experimental study of frost accumulation on fan-supplied tube-fin evaporators [J].
da Silva, Diogo L. ;
Hermes, Christian J. L. ;
Melo, Claudio .
APPLIED THERMAL ENGINEERING, 2011, 31 (6-7) :1013-1020
[7]   Modeling the airside dynamic behavior of a heat exchanger under frosting conditions [J].
Gao, Tieyu ;
Gong, Jianying .
JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2011, 25 (10) :2719-2728
[8]   Experimental study on frost growth and dynamic performance of air source heat pump system [J].
Guo, Xian-Min ;
Chen, Yi-Guang ;
Wang, Wei-Hua ;
Chen, Chun-Zheng .
APPLIED THERMAL ENGINEERING, 2008, 28 (17-18) :2267-2278
[9]   Numerical prediction of frost properties and performance of fin-tube heat exchanger with plain fin under frosting [J].
Hwang, Jieun ;
Cho, Keumnam .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 46 :59-68
[10]   Thermal performance of microchannel heat exchangers according to the design parameters under the frosting conditions [J].
Kim, Kyoungmin ;
Kim, Min-Hwan ;
Kim, Dong Rip ;
Lee, Kwan-Soo .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 71 :626-632