Improved Capacitor Voltage Feedforward for Three-Phase LCL-Type Grid-Connected Converter to Suppress Start-Up Inrush Current

被引:11
作者
Zhou, Shiying [1 ]
Zou, Xudong [1 ]
Zhu, Donghai [1 ]
Tong, Li [2 ]
Kang, Yong [1 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Peoples R China
[2] Zhejiang Elect Power Corp Res Inst, Hangzhou 310014, Zhejiang, Peoples R China
关键词
capacitor voltage feedforward; LCL-type grid-connected converter; stability; start-up inrush current; weak grid; CONTROL STRATEGY; WIND TURBINE; FILTER; CONTROLLER; INVERTERS;
D O I
10.3390/en10050713
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Three-phase active damping LCL-type grid-connected converters are usually used in distributed power generation systems. However, serious inrush current will be aroused when the grid-connected converter starts, especially in rectifier mode, if no effective control method is taken. The point of common coupling (PCC) voltage feedforward is usually used to suppress start-up inrush current. Unfortunately, it will introduce a positive feedback loop related to the grid current and grid impedance under weak grid conditions, and therefore, the grid current will be distorted and the system stability margin will be significantly reduced. To solve the above problems, this paper proposes a simple method based on a d-axis fundamental positive-sequence component of filter capacitor voltage feedforward, without extra sensors and software resources. With the proposed method, it is possible to suppress the start-up inrush current and maintain the grid current quality and system stability under weak grid conditions. The mechanism of start-up inrush current and the effectiveness of the method for inrush current suppression are analyzed in detail. Then, the influences of different feedforward methods on system stability are analyzed under weak grid conditions by the impedance model of grid-connected converter. Finally, experimental results verify the validity of the proposed method.
引用
收藏
页数:19
相关论文
共 30 条
[11]   Stability of photovoltaic and wind turbine grid-connected inverters for a large set of grid impedance values [J].
Liserre, M ;
Teodorescu, R ;
Blaabjerg, F .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2006, 21 (01) :263-272
[12]   Multiple harmonics control for three-phase grid converter systems with the use of PI-RES current controller in a rotating frame [J].
Liserre, Marco ;
Teodorescu, Remus ;
Blaabjerg, Frede .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2006, 21 (03) :836-841
[13]  
Lu M, 2016, IEEE ANN SO POW EL C, V2nd, DOI [10.1109/SPEC.2016.7846173, DOI 10.1109/SPEC.2016.7846173]
[14]  
Qu B, 2009, IEEE INT POWER ELEC, P2204
[15]   Improved Vector Control Strategy for Current-Source Converters Connected to Very Weak Grids [J].
Radwan, Amr Ahmed A. ;
Mohamed, Yasser Abdel-Rady I. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2016, 31 (04) :3238-3248
[16]   Decoupled double synchronous reference frame PLL for power converters control [J].
Rodriguez, Pedro ;
Pou, Josep ;
Bergas, Joan ;
Candela, J. Ignacio ;
Burgos, Rolando P. ;
Boroyevich, Dushan .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2007, 22 (02) :584-592
[17]   Dual current control scheme for PWM converter under unbalanced input voltage conditions [J].
Song, HS ;
Nam, K .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 1999, 46 (05) :953-959
[18]   Impedance-Based Stability Criterion for Grid-Connected Inverters [J].
Sun, Jian .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2011, 26 (11) :3075-3078
[19]   Grid-Current-Feedback Active Damping for LCL Resonance in Grid-Connected Voltage-Source Converters [J].
Wang, Xiongfei ;
Blaabjerg, Frede ;
Loh, Poh Chiang .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2016, 31 (01) :213-223
[20]   Grid Harmonics Suppression Scheme for LCL-Type Grid-Connected Inverters Based on Output Admittance Revision [J].
Wu, Xiaojie ;
Li, Xiaoqiang ;
Yuan, Xibo ;
Geng, Yiwen .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2015, 6 (02) :411-421