Improved Capacitor Voltage Feedforward for Three-Phase LCL-Type Grid-Connected Converter to Suppress Start-Up Inrush Current

被引:11
作者
Zhou, Shiying [1 ]
Zou, Xudong [1 ]
Zhu, Donghai [1 ]
Tong, Li [2 ]
Kang, Yong [1 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Peoples R China
[2] Zhejiang Elect Power Corp Res Inst, Hangzhou 310014, Zhejiang, Peoples R China
关键词
capacitor voltage feedforward; LCL-type grid-connected converter; stability; start-up inrush current; weak grid; CONTROL STRATEGY; WIND TURBINE; FILTER; CONTROLLER; INVERTERS;
D O I
10.3390/en10050713
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Three-phase active damping LCL-type grid-connected converters are usually used in distributed power generation systems. However, serious inrush current will be aroused when the grid-connected converter starts, especially in rectifier mode, if no effective control method is taken. The point of common coupling (PCC) voltage feedforward is usually used to suppress start-up inrush current. Unfortunately, it will introduce a positive feedback loop related to the grid current and grid impedance under weak grid conditions, and therefore, the grid current will be distorted and the system stability margin will be significantly reduced. To solve the above problems, this paper proposes a simple method based on a d-axis fundamental positive-sequence component of filter capacitor voltage feedforward, without extra sensors and software resources. With the proposed method, it is possible to suppress the start-up inrush current and maintain the grid current quality and system stability under weak grid conditions. The mechanism of start-up inrush current and the effectiveness of the method for inrush current suppression are analyzed in detail. Then, the influences of different feedforward methods on system stability are analyzed under weak grid conditions by the impedance model of grid-connected converter. Finally, experimental results verify the validity of the proposed method.
引用
收藏
页数:19
相关论文
共 30 条
[1]  
[Anonymous], IEEE T POWE IN PRESS
[2]   Overview of control and grid synchronization for distributed power generation systems [J].
Blaabjerg, Frede ;
Teodorescu, Remus ;
Liserre, Marco ;
Timbus, Adrian V. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (05) :1398-1409
[3]   A Time Delay Compensation Method Based on Area Equivalence For Active Damping of an LCL-Type Converter [J].
Chen, Chen ;
Xiong, Jian ;
Wan, Zhiqiang ;
Lei, Ji ;
Zhang, Kai .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2017, 32 (01) :762-772
[4]   Impedance-Phased Dynamic Control Method for Grid-Connected Inverters in a Weak Grid [J].
Chen, Xin ;
Zhang, Yang ;
Wang, Shanshan ;
Chen, Jie ;
Gong, Chunying .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2017, 32 (01) :274-283
[5]   Design-Oriented Study of Advanced Synchronous Reference Frame Phase-Locked Loops [J].
Golestan, Saeed ;
Monfared, Mohammad ;
Freijedo, Francisco D. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2013, 28 (02) :765-778
[6]   Start-Up Current Control Method for Three-Phase PWM Rectifiers with a Low Initial DC-Link Voltage [J].
Gu, Bon-Gwan ;
Choi, Jun-Hyuk ;
Jung, In-Soung .
JOURNAL OF POWER ELECTRONICS, 2012, 12 (04) :587-594
[7]  
He Jinping., 2014, 2014 IEEE Conference and Expo Transportation Electrification Asia-Pacific (ITEC Asia-Pacific), P1
[8]   DC-Bus Voltage Control Stability Affected by AC-Bus Voltage Control in VSCs Connected to Weak AC Grids [J].
Huang, Yunhui ;
Yuan, Xiaoming ;
Hu, Jiabing ;
Zhou, Pian ;
Wang, Dong .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2016, 4 (02) :445-458
[9]   A Control Design Approach for Three-Phase Grid-Connected Renewable Energy Resources [J].
Khajehoddin, S. Ali ;
Karimi-Ghartemani, Masoud ;
Jain, Praveen K. ;
Bakhshai, Alireza .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2011, 2 (04) :423-432
[10]   Full-Feedforward Schemes of Grid Voltages for a Three-Phase LCL-Type Grid-Connected Inverter [J].
Li, Weiwei ;
Ruan, Xinbo ;
Pan, Donghua ;
Wang, Xuehua .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (06) :2237-2250