An interim dynamic induction motor model for stability studies in the WSCC

被引:122
作者
Pereira, L [1 ]
Kosterev, D
Mackin, P
Davies, D
Undrill, J
Zhu, WC
机构
[1] No Calif Power Agcy, Roseville, CA 95678 USA
[2] Bonneville Power Adm, Vancouver, WA USA
[3] Calif ISO, Folsom, CA 95630 USA
[4] Western Syst Coordinating Council, Salt Lake City, UT 84108 USA
[5] Gen Elect Int Inc, Schenectady, NY 12345 USA
关键词
induction motor; load modeling; power system dynamic modeling; power system dynamic performance; transient stability;
D O I
10.1109/TPWRS.2002.804960
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An "interim" composite load model containing a static part and a dynamic part has been implemented in the Western Systems Coordinating Council (WSCC). The static part of the load model is about 80% of the total load and comprises of existing static load data from the WSCC members. The dynamic part is a default induction motor model for approximately 20% of the total load. This composite model is used for all loads in the full-scale WSCC grid models that are the basis for system interconnection studies. The model is designed primarily to capture the effects of dynamic induction motor loads for highly stressed north to south flow conditions during summer peaks in the WSCC.
引用
收藏
页码:1108 / 1115
页数:8
相关论文
共 10 条
[1]   LOAD REPRESENTATION IN POWER SYSTEM STABILITY STUDIES [J].
CONCORDIA, C ;
IHARA, S .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (04) :969-977
[2]   The effect of load models on unstable low-frequency oscillation damping in taipower system experience w/wo power system stabilizers [J].
Kao, WS .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2001, 16 (03) :463-472
[3]  
KOSTEREV D, 2000, MODEL VALIDATION ANA
[4]   Model validation for the August 10, 1996 WSCC system outage [J].
Kosterev, DN ;
Taylor, CW ;
Mittelstadt, WA .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1999, 14 (03) :967-974
[5]   VOLTAGE DEPENDENCE OF COMPOSITE LOADS IN POWER-SYSTEMS [J].
OHYAMA, T ;
WATANABE, A ;
NISHIMURA, K ;
TSURUTA, S .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1985, 104 (11) :3064-3073
[6]   Aspects of voltage responses of induction motor loads [J].
Omata, T ;
Uemura, K .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1998, 13 (04) :1337-1344
[7]  
PRICE WW, 1993, IEEE T POWER SYST, V8, P472
[8]   STANDARD LOAD MODELS FOR POWER-FLOW AND DYNAMIC PERFORMANCE SIMULATION [J].
PRICE, WW ;
TAYLOR, CW ;
ROGERS, GJ ;
SRINIVASAN, K ;
CONCORDIA, C ;
PAL, MK ;
BESS, KC ;
KUNDUR, P ;
AGRAWAL, BL ;
LUINI, JF ;
VAAHEDI, E ;
JOHNSON, BK .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (03) :1302-1313
[9]   MODEL SELECTION AND DATA ASSEMBLY FOR POWER SYSTEM SIMULATIONS [J].
UNDRILL, JM ;
LASKOWSKI, TF .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (09) :3333-3341
[10]  
*WSCC MOD VAL WORK, 1997, TEST GUID SYNCHR UN