SISO Equivalent of MIMO VSC-Dominated Power Systems for Voltage Amplitude and Phase Dynamic Analyses in Current Control Timescale

被引:51
作者
Li, Sheng [1 ,2 ]
Yan, Yabing [1 ,2 ]
Yuan, Xiaoming [1 ,2 ]
机构
[1] Huazhong Univ Sci & Technol, State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Hubei, Peoples R China
[2] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, Wuhan 430074, Hubei, Peoples R China
关键词
SISO equivalent; voltage source converter (VSC); current control timescale; voltage amplitude and phase; modeling; multi-VSC; interaction; STABILITY ANALYSIS;
D O I
10.1109/TEC.2019.2908222
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
High-frequency oscillations caused by voltage source converters (VSCs) in current control timescale (less than 20 ms) have brought great challenges to the security and stable operation of the VSC-dominated power systems. However, relevant studies on this multi-input multi-output (MIMO) system still lack enough mechanism cognitions of its voltage amplitude/phase dynamics. Thus, this paper will propose a single-input single-output (SISO) equivalent method of this MIMO system to separately study its amplitude/phase dynamics. First, a linearized VSC model based on internal voltage motion equation in current control timescale is derived. This model can explicitly depict VSC's self-characteristic, which is suitable for multi-VSC voltage amplitude/phase dynamic analyses. Then, with reserving and converting the interactions of other outputs into one output, the MIMO system based on this VSC model can be equivalent into the amplitude motion and the phase motion, respectively. These two SISO systems are extremely convenient for engineers to study the mechanisms of the voltage amplitude/phase dynamics. Besides, this SISO equivalent method of the MIMO system can also be used to quantitatively analyze the interactions among the multi-VSC. Finally, the application of this method is illustrated in a single VSC system and the time domain simulations validate the correctness of the analyses.
引用
收藏
页码:1454 / 1465
页数:12
相关论文
共 25 条
[1]  
[Anonymous], 2014, THESIS
[2]   EXPERIENCE WITH HVDC - TURBINE-GENERATOR TORSIONAL INTERACTION AT SQUARE BUTTE [J].
BAHRMAN, M ;
LARSEN, EV ;
PIWKO, RJ ;
PATEL, HS .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (03) :966-975
[3]  
Buchhagen C., 2015, ETG FB 147 INT ETG C
[4]   Impedance Modeling and Analysis of Grid-Connected Voltage-Source Converters [J].
Cespedes, Mauricio ;
Sun, Jian .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (03) :1254-1261
[5]  
de Bosio F, 2015, IEEE IND ELEC, P5322, DOI 10.1109/IECON.2015.7392938
[6]   Input-admittance calculation and shaping for controlled voltage-source converters [J].
Harnefors, Lennart ;
Bongiorno, Massimo ;
Lundberg, Stefan .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2007, 54 (06) :3323-3334
[7]   Inertia Provision and Estimation of PLL-Based DFIG Wind Turbines [J].
He, Wei ;
Yuan, Xiaoming ;
Hu, Jiabing .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (01) :510-521
[8]   Modeling of DFIG-Based WTs for Small-Signal Stability Analysis in DVC Timescale in Power Electronized Power Systems [J].
Hu, Jiabing ;
Yuan, Hao ;
Yuan, Xiaoming .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2017, 32 (03) :1151-1165
[9]   State-space model of grid-connected inverters under current control mode [J].
Kroutikova, N. ;
Hernandez-Aramburo, C. A. ;
Green, T. C. .
IET ELECTRIC POWER APPLICATIONS, 2007, 1 (03) :329-338
[10]  
Kundur P, 1994, POWER SYSTEM STABILI