Hybrid solutions for improving passive filter performance in high power applications

被引:209
作者
Bhattacharya, S [1 ]
Cheng, PT [1 ]
Divan, DM [1 ]
机构
[1] SOFT SWITCHING TECHNOL CORP, MIDDLETON, WI 53562 USA
关键词
active inductance; harmonic compensation; hybrid active filter system; IEEE 519 harmonic standard; parallel hybrid active filter system; synchronous reference frame;
D O I
10.1109/28.585864
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper presents a new control scheme for a parallel hybrid active filter system intended for harmonic compensation of large nonlinear loads up to 50 MVA, to meet IEEE 519 recommended harmonic standards, The active filter is small rated, 2%-3% of load kilovoltampere rating, The control scheme is based on the concept of synthesizing a dynamically variable inductance, and its usefulness is demonstrated for an active filtering application, A synchronous reference frame (SRF) controller implements the dynamically varying negative or positive inductance by generating active filter inverter voltage commands, This variable inductance controller parallel hybrid active filter system can selectively synthesize multiple ''active inductances'' at dominant harmonic frequencies without affecting passive filter impedances at all other frequencies, This controller also provides a ''current limiting'' function to prevent passive filter overloading under ambient harmonic loads and/or supply voltage distortions, Three implementation variations of a parallel hybrid active filter system are presented, This paper also proposes the use of power factor correction capacitors as low cost passive filters for a parallel hybrid active filter system, which are controlled to provide either single or multiple tuned harmonic sinks and to increase cost effectiveness for high power applications, Simulation results with small rated pulsewidth modulated (PWM) and square-wave active filter inverters validate the proposed variable inductance controller operation for mistuned passive filters, to provide single and multiple frequency tuning to achieve harmonic compensation of a 325 kVA harmonic load under supply voltage harmonics and ambient harmonic loads.
引用
收藏
页码:732 / 747
页数:16
相关论文
共 25 条
[1]   CONTROL STRATEGY OF ACTIVE POWER FILTERS USING MULTIPLE VOLTAGE-SOURCE PWM CONVERTERS [J].
AKAGI, H ;
NABAE, A ;
ATOH, S .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1986, 22 (03) :460-465
[2]   Control strategy and site selection of a shunt active filter for damping of harmonic propagation in power distribution systems [J].
Akagi, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) :354-363
[3]  
Akagi H., 1995, EPE '95. 6th European Conference on Power Electronics and Applications, P17
[4]   HARMONIC REDUCTION IN THYRISTOR CONVERTERS BY HARMONIC CURRENT INJECTION [J].
AMETANI, A .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1976, 95 (02) :441-449
[5]  
Bhattacharya S, 1996, IEEE IND APPLIC SOC, P1106, DOI 10.1109/IAS.1996.560218
[6]  
Bhattacharya S, 1995, IEEE IND APPLIC SOC, P2531, DOI 10.1109/IAS.1995.530625
[7]  
BHATTACHARYA S, 1993, IEEE POWER ELECTRON, P779, DOI 10.1109/PESC.1993.472012
[8]  
Bhattacharya S, 1995, IEEE IND APPLIC SOC, P2357, DOI 10.1109/IAS.1995.530602
[9]  
BHATTACHARYA S, 1996, IEEE POW EL DRIV EN, P1078
[10]  
BHATTACHARYA S, 1991, EPE, V3, P30