Contamination Level Prediction of Insulators Based on the Characteristics of Leakage Current

被引:63
作者
Li, Jingyan [1 ]
Sun, Caixin [1 ]
Sima, Wenxia [1 ]
Yang, Qing [1 ]
Hu, Jianlin [1 ]
机构
[1] Chongqing Univ, Coll Elect Engn, State Key Lab Power Transmiss Equipment & Syst Sa, Chongqing 400044, Peoples R China
关键词
Contamination flashover; contamination prediction; insulator; leakage current; neural network model; prediction characteristics; CURRENT WAVE-FORMS; FREQUENCY-CHARACTERISTICS; SILICONE-RUBBER; NEURAL-NETWORK; FLASHOVER; VOLTAGE;
D O I
10.1109/TPWRD.2009.2035426
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In order to assess how severe the contamination level of the surface of power line insulators and to prevent unpredictable contamination flashovers, it is important to seek optimal prediction characteristics. That leads to the increase of the warning time and to the improvement of the reliability of the pre-warning system. Nearly 30 insulator strings at five pollution levels were tested in an artificial fog chamber, where their leakage currents were continuously recorded at the same operation conditions. The three characteristics of the leakage current, namely the mean value, maximum value, and the standard deviation of the root-mean-square (RMS) value of the leakage current, have been extracted. They describe jointly the current contamination levels of an insulator surface. In addition, regression equations between the three characteristics and various contamination levels have been established. The same three characteristics have been selected and used as the inputs of a neural network model together with two more parameters, the relative humidity and operating voltage. Also, the influence of each characteristic on the contamination prediction results has been investigated. The model is appropriate to predict the equivalent salt deposit densities (ESDD) with a difference of less than 0.035 mg/cm if the training data and the testing data are selected at the security stage. This research results in the optimal prediction input parameters and sufficient pre-warning time before a contamination flashover.
引用
收藏
页码:417 / 424
页数:8
相关论文
共 21 条
[21]  
YAO CG, 2007, T CSEE, V27, P1