A review on energy piles design, sizing and modelling

被引:105
作者
Fadejev, Jevgeni [1 ,2 ]
Simson, Raimo [1 ]
Kurnitski, Jarek [1 ,2 ]
Haghighat, Fariborz [3 ]
机构
[1] Tallinn Univ Technol, Ehitajate Tee 5, EE-19086 Tallinn, Estonia
[2] Aalto Univ, Sch Engn, Rakentajanaukio 4 A, FI-02150 Espoo, Finland
[3] Concordia Univ, Dept Bldg Civil & Environm Engn, Montreal, PQ H3G 1M8, Canada
关键词
Energy piles; Sizing; Modelling; Fundamental scheme; Thermal storage; GROUND HEAT-EXCHANGERS; THERMAL RESPONSE; PERFORMANCE; SYSTEM; BOREHOLE; STORAGE; FOUNDATIONS; TEMPERATURE; PUMPS;
D O I
10.1016/j.energy.2017.01.097
中图分类号
O414.1 [热力学];
学科分类号
摘要
Boreholes and energy piles coupled with ground source heat pump plants utilize renewable geothermal energy for buildings heating and cooling purposes and need proper design and sizing in order to end up with high plant efficiency. This paper conducted a review of available scientific literature, design standards and guidelines on energy piles performance within the framework of the lEA-ECES Annex 31. Main aspects covered were typical plant solutions, configurations of energy piles and their thermal response test performance, available analytical and numerical models with their main features and application in commercial software and design manuals. Four typical fundamental schemes of geothermal plant with energy piles were found, both suitable for cold and hot climate applications. Properly sized heat pump systems with energy piles were characterized with high overall system SCOP values higher than 4.5, while some case studies reported two times smaller SCOP values that illustrates the effect of proper design and sizing of such systems. The lack of specific heat extraction values which could be determined based on the climate and energy pile application show the need to develop general procedures for early stage energy pile sizing that would allow quick estimates of the heat extraction rejection potential and system performance with reasonable accuracy for conceptual design. Most of available software is borehole oriented and will fit for energy piles sizing if software supports variable ground surface temperature boundary conditions, which, however is not implemented in most of software packages. Expected software features to be implemented are water advection and multiregional surface boundary heat transfer. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:390 / 407
页数:18
相关论文
共 80 条
  • [1] Hybrid ground-source heat pump system with active air source regeneration
    Allaerts, K.
    Coomans, M.
    Salenbien, R.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2015, 90 : 230 - 237
  • [2] Experimental and computational investigation of multi U-tube boreholes
    Aydin, Murat
    Sisman, Altug
    [J]. APPLIED ENERGY, 2015, 145 : 163 - 171
  • [3] Finite cylinder-source model for energy pile heat exchangers: Effects of thermal storage and vertical temperature variations
    Bandos, Tatyana V.
    Campos-Celador, Alvaro
    Lopez-Gonzalez, Luis M.
    Sala-Lizarraga, Jose M.
    [J]. ENERGY, 2014, 78 : 639 - 648
  • [4] Bixel H.C., 1967, SOC PET ENG J, V7, P301, DOI DOI 10.2118/1516-PA
  • [5] Blocon, 2015, EARTH EN DES V 3 2 U
  • [6] NUMERICAL SOLUTION OF PHASE-CHANGE PROBLEMS
    BONACINA, C
    COMINI, G
    FASANO, A
    PRIMICERIO, M
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1973, 16 (10) : 1825 - 1832
  • [7] Energy foundations and other thermo-active ground structures
    Brandl, H
    [J]. GEOTECHNIQUE, 2006, 56 (02): : 81 - 122
  • [8] Brandl H., 1998, Proceedings of 7th International Conference and Exhibition on Piling and Deep Foundations, P341
  • [9] Thermo-Active Ground-Source Structures for Heating and Cooling
    Brandl, Heinz
    [J]. MODERN BUILDING MATERIALS, STRUCTURES AND TECHNIQUES, 2013, 57 : 9 - 18
  • [10] Carslaw H.S., 1947, HEAT CONDUCTION SOLI