Electric Field and Thermal Analysis of 132 kV Ceramic Oil-Filled Cable Sealing Ends

被引:11
|
作者
Zachariades, Christos [1 ]
Peesapati, Vidyadhar [2 ]
Gardner, Richard [3 ]
Cwikowski, Oliver [4 ]
机构
[1] Univ Liverpool, Elect Energy, Liverpool L69 3BX, Merseyside, England
[2] Univ Manchester, Area High Voltage Syst Asset Management & Condit, Manchester M13 9PL, Lancs, England
[3] Univ Manchester, Natl Grid Power Syst Res Ctr, Manchester M13 9PL, Lancs, England
[4] Natl Grid Plc, Warwick CV34 6DA, England
基金
英国工程与自然科学研究理事会;
关键词
Cable sealing end (CSE); cable termination; condition monitoring; electric field; finite element analysis (FEA); simulation; thermal imaging;
D O I
10.1109/TPWRD.2020.2977728
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper reports on a method combining the use of finite element simulations and external measurements to provide preliminary condition diagnosis of oil-filled cable sealing ends (CSEs) without requiring downtime. Good agreement has been obtained between the predictions from the electric field and thermal simulations and the measurements on a 132 kV oil-filled CSE. The electrostatic computation combined with electric field measurements can provide information regarding the electric field distribution inside the CSE and help in identifying potential issues with the CSE design, the materials or the cable termination process. The thermal computation combined with thermal imaging can reveal potential problems, such as high resistance connection to the busbar, and provide information regarding the cooling efficiency of the liquid dielectric. The method presented can provide the starting point for prioritizing maintenance operations on CSEs.
引用
收藏
页码:311 / 319
页数:9
相关论文
共 50 条
  • [1] Investigation of incipient faults in 66 kV oil-filled cable sealing ends
    Peesapati, Vidyadhar
    Zachariades, Christos
    Callender, George
    Gao, Siyu
    Cwikowski, Oliver
    Gardner, Richard
    HIGH VOLTAGE, 2022, 7 (04) : 666 - 675
  • [2] 500 KV OIL-FILLED CABLE INSTALLED ON BRIDGES
    MINEMURA, S
    MAEKAWA, Y
    IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (02) : 840 - 845
  • [3] Field measurement and simulation of electromagnetic transients on 132 kV oil-filled submarine cables
    Gustavsen, Bjorn
    Hoidalen, Hans Kristian
    Ohnstad, Trond M.
    ELECTRIC POWER SYSTEMS RESEARCH, 2014, 115 : 43 - 49
  • [4] THERMAL ANALYSIS OF CABLE SEALING ENDS.
    Aziz, M.M.Abdel
    Riege, H.
    Proceedings of the Annual Reliability and Maintainability Symposium, 1980,
  • [5] THERMAL-ANALYSIS OF CABLE SEALING ENDS
    AZIZ, MMA
    RIEGE, H
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (02): : 829 - 832
  • [6] Study of Thermal Field Analysis Methods of Oil-Filled Motors
    Huang, Juyan
    Xu, Yongxiang
    Xiao, Lijun
    Zhuo, Liang
    Yu, Guodong
    Zou, Jibin
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2024, 34 (08) : 1 - 5
  • [7] The Degradation Analysis of PVC Insulation Tape in 220kV Oil-filled Cable Terminal
    Yu, Shihu
    Yu, Xin
    Zhao, Yaohong
    Wang, Qing
    Yang, Xian
    Wang, Shihang
    2020 8TH INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD 2020), 2020, : 408 - 411
  • [8] 275 kV OIL-FILLED SUBMARINE CABLE INSTALLATION IN HONG KONG.
    Yee, E.L.Y.
    Kan, C.H.
    Eguchi, Kikuo
    Murakami, Kaihei
    Suzuki, Kenshi
    1983,