IMPROVEMENT AND SENSITIVITY ANALYSIS OF EQUIVALENT HEAT TRANSFER MODEL FOR DYNAMIC THERMAL RATING OF OVERHEAD LINES

被引:0
作者
Peng, Xiangyang [1 ]
Deng, Honglei [2 ]
Wang, Rui [1 ]
Liu, Zhao [2 ]
Luo, Shujian [1 ]
Guo, Deming [2 ]
Liu, Gang [2 ]
机构
[1] Guangdong Power Grid Co Ltd, Elect Power Res Inst, Guangdong Key Lab Elect Power Equipment Reliabil, Guangzhou, Peoples R China
[2] South China Univ Technol, Sch Elect Power Engn, Guangzhou, Peoples R China
来源
THERMAL SCIENCE | 2022年 / 26卷 / 06期
关键词
conductor ampacity; improved EHT model; sensitivity analysis; overhead lines; and heat transfer;
D O I
10.2298/TSCI210611020P
中图分类号
O414.1 [热力学];
学科分类号
摘要
With the rapid growth of power demand, the conductor ampacity calculation method based on the dynamic thermal rating (DTR) becomes more and more important. Based on the shortcomings of the current DTR models, a new DTR model that does not need to measure the wind speed and the operating state of conductor is proposed, which is called the equivalent heat transfer (EHT) model. However, there are still shortcomings in the accuracy of the EHT model in application. In this paper, the EHT model is improved at first according to the consideration of the effect of air physical parameters and the redetermination of the experimental parameters of the EHT equipment. Then, the operation of EHT equipment is simulated through the established experimental platform. The improved EHT model is verified by the IEEE standard. Finally, the sensitivity analysis of the improved EHT model is carried out. The results show that the improved EHT model is greatly improved on application accuracy compared to the original EHT model. Moreover, the improved EHT model can choose the steady-state temperature at any position on the surface of the aluminum ball to calculate the conductor ampacity, and the relative error does not exceed 6%. The improved EHT model is reliable and can meet the safe operation requirements of the power system in practical engineering applications.
引用
收藏
页码:4669 / 4683
页数:15
相关论文
共 22 条
[2]   Calculation of the overhead transmission line conductor temperature in real operating conditions [J].
Bena, Lubomir ;
Gall, Vladimir ;
Kanalik, Martin ;
Kolcun, Michal ;
Margitova, Anastazia ;
Meszaros, Alexander ;
Urbansky, Jakub .
ELECTRICAL ENGINEERING, 2021, 103 (02) :769-780
[3]   Smart Transmission Grid Applications and Their Supporting Infrastructure [J].
Bose, Anjan .
IEEE TRANSACTIONS ON SMART GRID, 2010, 1 (01) :11-19
[4]   Study of different mathematical approaches in determining the dynamic rating of overhead power lines and a comparison with real time monitoring data [J].
Castro, P. ;
Arroyo, A. ;
Martinez, R. ;
Manana, M. ;
Domingo, R. ;
Laso, A. ;
Lecuna, R. .
APPLIED THERMAL ENGINEERING, 2017, 111 :95-102
[5]   DYNAMIC LINE RATING IN THE OPERATING ENVIRONMENT [J].
FOSS, SD ;
MARAIO, RA .
IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (02) :1095-1106
[6]   An Improved Dynamic Thermal Current Rating Model for PMU-Based Wide Area Measurement Framework for Reliability Analysis Utilizing Sensor Cloud System [J].
Hasan, Mohammad Kamrul ;
Ahmed, Musse Mohamud ;
Musa, Sherfriz Sherry ;
Islam, Shayla ;
Abdullah, Siti Norul Huda Sheikh ;
Hossain, Eklas ;
Nafi, Nazmus Shaker ;
Vo, Nguyen .
IEEE ACCESS, 2021, 9 (09) :14446-14458
[7]  
House K.E., 1958, ELECTR ENG, V77, P719
[8]   Polymer composite materials: A comprehensive review [J].
Hsissou, Rachid ;
Seghiri, Rajaa ;
Benzekri, Zakaria ;
Hilali, Miloudi ;
Rafik, Mohamed ;
Elharfi, Ahmed .
COMPOSITE STRUCTURES, 2021, 262
[9]  
Hua G. W, 2021, GUANGDONG ELECT POWE, V34, P19
[10]   Temperature calculation of overhead power line conductors based on CIGRE Technical Brochure 601 in Slovakia [J].
Kanalik, Martin ;
Margitova, Anastazia ;
Bena, L'ubomir .
ELECTRICAL ENGINEERING, 2019, 101 (03) :921-933