Wind-tunnel analysis of natural ventilation in a generic building in sheltered and unsheltered conditions: Impact of Reynolds number and wind direction

被引:24
|
作者
Golubic, Dino [1 ,2 ]
Meile, Walter [2 ]
Brenn, Guenter [2 ]
Kozmar, Hrvoje [1 ]
机构
[1] Univ Zagreb, Fac Mech Engn & Naval Architecture, Ivana Lucica 5, Zagreb 10000, Croatia
[2] Graz Univ Technol, Inst Fluid Mech & Heat Transfer, Inffeldgasse 25-F, A-8010 Graz, Austria
关键词
Generic building; Suburban terrain; Flow velocity and direction; Cross- and single-sided ventilation; Unsheltered and sheltered conditions; Spacing density of buildings; Wind-tunnel experiments; CROSS-VENTILATION; FULL-SCALE; AIR-FLOW; CFD SIMULATION; BUOYANCY; DRIVEN; PRESSURES; ENCLOSURE; DESIGN; MODEL;
D O I
10.1016/j.jweia.2020.104388
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Natural ventilation is generally preferred to mechanical ventilation because it saves energy and protects the outdoor atmospheric environment. The present work focuses on the air change rate (ACH) of a generic building for single-sided and cross-ventilation arrangements. This topic was studied on small-scale building models of cubic shape in a boundary layer wind tunnel. Experiments were carried out by simulating the atmospheric boundary layer (ABL) over suburban terrain that impinges a building model standing alone or surrounded by other buildings in a symmetrical 3 x 3 pattern. The spacing density of building models, flow incidence angle, velocity, and ventilation arrangement were major parameters for quantifying the ventilation performance. Hot-wire anemometry was used to determine the flow characteristics, and a tracer gas system was applied to measure the ACH. The ACH obtained for the isolated building proved larger than for the sheltered case, as expected. In the latter case, the ventilation is more efficient for less densely spaced buildings. For the isolated building, a linear relationship between the ACH and the flow velocity can be justified for both ventilation types. For the cross-ventilation setup, a model equation is proposed. It quantifies the dependence of the ACH on the flow velocity and incidence angle.
引用
收藏
页数:17
相关论文
共 50 条
  • [1] Wind tunnel experiments on cross-ventilation flow of a generic building with contaminant dispersion in unsheltered and sheltered conditions
    Tominaga, Yoshihide
    Blocken, Bert
    BUILDING AND ENVIRONMENT, 2015, 92 : 452 - 461
  • [2] WIND-TUNNEL INVESTIGATIONS OF NATURAL VENTILATION
    CERMAK, JE
    POREH, M
    PETERKA, JA
    AYAD, SS
    JOURNAL OF TRANSPORTATION ENGINEERING-ASCE, 1984, 110 (01): : 67 - 79
  • [3] INTERMITTENT HIGH REYNOLDS-NUMBER WIND-TUNNEL
    STOLLERY, JL
    MURTHY, AV
    AERONAUTICAL QUARTERLY, 1977, 28 (NOV): : 259 - 264
  • [4] Wind tunnel experiments on cross-ventilation flow of a generic sheltered building in urban areas
    Shirzadi, Mohammadreza
    Tominaga, Yoshihide
    Mirzaei, Parham A.
    BUILDING AND ENVIRONMENT, 2019, 158 : 60 - 72
  • [5] Correction of wind-tunnel pressure coefficients for Reynolds number effect
    Hoxey, RP
    Robertson, AP
    Richardson, GM
    Short, JL
    JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 1997, 71 : 547 - 555
  • [6] Numerical optimization and wind-tunnel testing of low Reynolds number airfoils
    Lutz, T
    Würz, W
    Wagner, S
    FIXED AND FLAPPING WING AERODYNAMICS FOR MICRO AIR VEHICLE APPLICATIONS, 2002, 195 : 169 - 190
  • [7] LANGLEY CRYOGENIC HIGH REYNOLDS-NUMBER WIND-TUNNEL PROGRAM
    POLHAMUS, EC
    KILGORE, RA
    ADCOCK, JB
    RAY, EJ
    ASTRONAUTICS & AERONAUTICS, 1974, 12 (10): : 30 - 40
  • [8] Wind tunnel test on wind natural ventilation building with different partitions
    Guan, Yanling (guanyl1@163.com), 1600, Science Press (37):
  • [9] Cross-ventilation in a generic isolated building equipped with louvers: Wind-tunnel experiments and CFD simulations
    Kosutova, Katarina
    van Hooff, Twan
    Vanderwel, Christina
    Blocken, Bert
    Hensen, Jan
    BUILDING AND ENVIRONMENT, 2019, 154 : 263 - 280
  • [10] Wind tunnel investigation on influence of fluctuating wind direction on cross natural ventilation
    Ji, Liang
    Tan, Hongwei
    Kato, Shinsuke
    Bu, Zhen
    Takahashi, Takeo
    BUILDING AND ENVIRONMENT, 2011, 46 (12) : 2490 - 2499