Understanding the Impact of Moisture and Ageing of Transformer Insulation on Frequency Domain Spectroscopy

被引:8
作者
Jadav, Raj B. [1 ]
Ekanayake, Chandima [1 ]
Saha, Tapan K. [1 ]
机构
[1] Univ Queensland, Sch Informat Technol & Elect Engn, St Lucia, Qld 4072, Australia
关键词
Ageing; paper insulation; frequency domain spectroscopy; moisture; OIL IMPREGNATED CELLULOSE; POWER TRANSFORMERS; DIELECTRIC RESPONSE; PAPER INSULATION;
D O I
10.1109/TDEI.2013.003984
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Moisture is one of the most significant parameters that can accelerate ageing in paper/pressboard insulation. In order to understand the impact of moisture and ageing on Frequency Domain Spectroscopy (FDS) measurements, oil impregnated pressboard samples of different moisture contents are prepared and aged at 105 degrees C temperature. FDS measurements on pressboard samples are carried out at different ageing time. Other measurements such as moisture, degree of polymerization (DP), Furan and Dissolved Gas Analysis (DGA) are also performed on oil and pressboard samples. It is observed that FDS measurements on pressboard samples are mostly influenced by the moisture contents. Several other pressboard samples are prepared under different conditions to determine how FDS measurements are affected by moisture, aged oil and ageing of pressboard sample considering each of the parameter individually as well as in different combinations. Results suggest that FDS measurements are sensitive to the change in moisture, ageing products and ageing of pressboard (DP) sample. However, impact of ageing products and ageing of pressboard sample (DP) on FDS measurements are smaller in comparison to moisture.
引用
收藏
页码:369 / 379
页数:11
相关论文
共 16 条
  • [1] [Anonymous], 2007, AG CELL MIN OIL INS, V323
  • [2] Furan Analysis for Liquid Power Transformers
    Cheim, Luiz
    Platts, Donald
    Prevost, Thomas
    Xu, Shuzhen
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2012, 28 (02) : 8 - 21
  • [3] Moisture equilibrium in transformer paper-oil systems
    Du, Y
    Zahn, M
    Lesieutre, BC
    Mamishev, AV
    Lindgren, SR
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 1999, 15 (01) : 11 - 20
  • [4] Emsley A. M., 1992, Sixth International Conference on Dielectric Materials, Measurements and Applications (Conf. Publ. No.363), P229
  • [5] REVIEW OF CHEMICAL INDICATORS OF DEGRADATION OF CELLULOSIC ELECTRICAL PAPER INSULATION IN OIL-FILLED TRANSFORMERS
    EMSLEY, AM
    STEVENS, GC
    [J]. IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 1994, 141 (05) : 324 - 334
  • [6] Does the Degree of Cellulose Polymerization Affect the Dielectric Response?
    Gielniak, Jaroslaw
    Graczkowski, Andrzej
    Moscicka-Grzesiak, Hanna
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (05) : 1647 - 1650
  • [7] Quantitative Analysis Ageing Status of Natural Ester-paper Insulation and Mineral Oil-paper Insulation by Polarization/Depolarization Current
    Hao, Jian
    Liao, Ruijin
    Chen, George
    Ma, Zhiqin
    Yang, Lijun
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (01) : 188 - 199
  • [8] Jadav R. B., 2012, 22 AUSTR U POW ENG C, P1
  • [9] Quantitative Analysis of Ageing Condition of Oil-paper Insulation by Frequency Domain Spectroscopy
    Liao, Ruijin
    Hao, Jian
    Chen, G.
    Yang, Lijun
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (03) : 821 - 830
  • [10] Dielectric response of mineral oil impregnated cellulose and the impact of aging
    Linhjell, Dag
    Lundgaard, Lars
    Gafvert, Uno
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2007, 14 (01) : 156 - 169