A line-interactive UPS system implementation with series-parallel active power-line conditioning for three-phase, four-wire systems

被引:22
作者
da Silva, SAO
Donoso-Garcia, P
Cortizo, PC
Seixas, PF
机构
[1] Univ Fed Minas Gerais, Dept Elect Engn, BR-31270901 Belo Horizonte, MG, Brazil
[2] CEFET PR, Dept Elect Engn, BR-86300000 Cornelio Procopio, PR, Brazil
关键词
active power filters; harmonics; uninterruptible power supply system; power factor correction; synchronous reference frame controller;
D O I
10.1016/j.ijepes.2003.11.008
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a three-phase line-interactive uninterruptible power supply (UPS) system with active series-parallel power-line conditioning capabilities. Synchronous reference frame (SRF)-based controller is used to harmonic and reactive power compensation generated from any configuration of non-linear load. Under normal line conditions the UPS system works with universal filtering capabilities, such as compensating the input currents and output voltages. Two three-phase pulse width inoculation (PWM) converters, called series and parallel active filters. are used to perform the series and parallel active power-line compensation. The series active power filter works as sinusoidal current source in phase with the input voltage, drawing from utility sinusoidal and balanced input currents with low total harmonic distortion (THD). The parallel active power filter works as sinusoidal voltage source in phase with the input voltage, providing regulated and sinusoidal Output voltages with low THD. Operation of a three-phase phase-locked loop (PLL) structure, used in the proposed line-interactive UPS implementation. is presented and experimentally verified under distorted utility conditions. The performance of the UPS system is evaluated in three-phase. four-wire systems. Digital simulations and experimental results are presented to confirm the theoretical studies. (C) 2004 Elsevier Ltd. All rights reserved.
引用
收藏
页码:399 / 411
页数:13
相关论文
共 12 条
[1]  
[Anonymous], P 7 APPL POW EL EXP
[2]  
Cheung R, 1996, IEEE POWER ELECTRON, P981, DOI 10.1109/PESC.1996.548701
[3]   A SURVEY OF NEUTRAL CURRENTS IN 3-PHASE COMPUTER POWER-SYSTEMS [J].
GRUZS, TM .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1990, 26 (04) :719-725
[4]  
Jeon SJ, 1997, IEEE POWER ELECTRON, P297, DOI 10.1109/PESC.1997.616740
[5]  
JOOS G, 1992, APPL POWER ELECT CO, P598, DOI 10.1109/APEC.1992.228356
[6]  
KAMRAN F, 1995, IEEE POWER ELECTRON, P500, DOI 10.1109/PESC.1995.474856
[7]   Operation of a phase locked loop system under distorted utility conditions [J].
Kaura, V ;
Blasko, V .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (01) :58-63
[8]  
LIN Y, 1993, APPL POWER ELECT CO, P533, DOI 10.1109/APEC.1993.290714
[9]  
QUINN CA, 1993, P IEEE APEC, P841
[10]  
SILVA SAO, 2001, P 36 IND APPL SOC AN, V4, P2389