Evaluation and improvement of the energy performance of a building's equipment and subsystems through continuous monitoring

被引:14
作者
Batista, Ana Paula [1 ,2 ]
Freitas, Maria Eugenia A. [2 ]
Jota, Fabio G. [1 ]
机构
[1] Univ Fed Minas Gerais, Grad Program Elect Engn, BR-31270901 Belo Horizonte, MG, Brazil
[2] CEFET MG, Fed Ctr Technol Educ, IERC, Ctr Intelligent Energy Res, BR-30510000 Belo Horizonte, MG, Brazil
关键词
Building monitoring; Modelling; Control; Equipment;
D O I
10.1016/j.enbuild.2014.02.029
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study proposes an experimental method for the evaluation of a building's equipment and subsystems through the continuous monitoring of electrical and environmental process variables. The aim of the study is to improve the building's comfort and energy performance using an automatic control system. A case study of a building's air-conditioning system is presented using the proposed method. A dynamic equipment-control model for an artificially conditioned environment is described. Additionally, empirical models are developed that relate equipment variables, the conditioned environment and a building's surroundings and occupation characteristics using representation through transfer functions and auto-regressive models with exogenous inputs (ARX). The empirical models were created using continuous monitoring data via the Internet and a low-cost platform known as the end use monitoring centre (EUMC). These models represent the relevant characteristics of the involved variables in consideration of the complexity of the modelled phenomena. An automatic equipment control system was designed and installed. The systems resulted in significant improvements in comfort and energy efficiency. The proposed method can be applied to diverse types of equipment and subsystems in buildings. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:368 / 381
页数:14
相关论文
共 29 条
[1]  
Batista A.P., 2006, THESIS PPGEE UFMG, P1
[2]  
Batista AP, 2007, BUILDING SIMULATION 2007, VOLS 1-3, PROCEEDINGS, P457
[3]   Empirical modeling of room air conditioners for building energy analysis [J].
Cherem-Pereira, G. ;
Mendes, N. .
ENERGY AND BUILDINGS, 2012, 47 :19-26
[4]   Description and validation of a computer based refrigeration system simulator [J].
Eames, I. W. ;
Brown, T. ;
Evans, J. A. ;
Maidment, G. G. .
COMPUTERS AND ELECTRONICS IN AGRICULTURE, 2012, 85 :53-63
[5]   Comparison of different controllers for variable speed compressor and electronic expansion valve [J].
Ekren, Orhan ;
Sahin, Savas ;
Isler, Yalcin .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (06) :1161-1168
[6]  
Electric Power Research Institute (EPRI), 2009, TECHNICAL REPORT
[7]   Study of the energy consumption of a massive free-running building in the Argentinean northwest through monitoring and thermal simulation [J].
Flores Larsen, Silvana ;
Filippin, Celina ;
Gonzalez, Silvina .
ENERGY AND BUILDINGS, 2012, 47 :341-352
[8]  
Freitas M.E., 2006, QUALIFICATION EXAM R, P1
[9]  
Freitas M. S. C., 2007, 2 BRAZ C EM EFF, P1
[10]   User behavior in whole building simulation [J].
Hoes, P. ;
Hensen, J. L. M. ;
Loomans, M. G. L. C. ;
de Vries, B. ;
Bourgeois, D. .
ENERGY AND BUILDINGS, 2009, 41 (03) :295-302