A Methodology for Power Quantities Calculation Applied to an FPGA-Based Smart-Energy Meter

被引:11
作者
Arenas, Luis De Oro [1 ]
Melo, Guilherme de Azevedo E. [1 ]
Canesin, Carlos A. [1 ]
机构
[1] Sao Paulo State Univ, UNESP, Power Elect Lab LEP, Elect Engn Dept, BR-15385000 Ilha Solteira, Brazil
基金
巴西圣保罗研究基金会;
关键词
Field-programmable gate array (FPGA)-based; IEEE; 1459-2010; Internet of Things (IoT); power quality (PQ); smart metering (SM); KEY MANAGEMENT; INFRASTRUCTURE; IMPLEMENTATION; SYSTEMS; DESIGN; IOT;
D O I
10.1109/TIM.2020.3034978
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A complete description of a field-programmable gate array (FPGA)-based smart energy meter is presented in this article. By implementing the power quantities definitions of the IEEE 1459-2010 Standard, a novel power quality analyzer capable of performing remote monitoring of electric power systems operating under sinusoidal, nonsinusoidal, balanced, and/or unbalanced conditions was developed. In order to ensure portability, the digital signal processing algorithms implemented on the FPGA device were entirely coded in hardware description languages, and all equations of them are fully described to be applied to any digital signal processing environment. These algorithms are completely defined as functions of the grid fundamental frequency, and by adjusting the sampling frequency, the adaptability of all modules developed is ensured. Experimental results were obtained using the developed platform in a three-phase four-wire system operating under several conditions, which were defined by the presence of harmonic components imposed by nonlinear loads and supply voltages, as well as by setting bidirectional power flow in distributed generation scenarios by employing a photovoltaic system. Real-time and parallel processes are validated as well.
引用
收藏
页数:11
相关论文
共 31 条
  • [1] Al Khuffash K, 2018, APPLICATION OF SMART GRID TECHNOLOGIES: CASE STUDIES IN SAVING ELECTRICITY IN DIFFERENT PARTS OF THE WORLD, P1, DOI 10.1016/B978-0-12-803128-5.00001-5
  • [2] Al-Eryan J., 2008, 32 BIT FLOATING POIN
  • [3] Syncretic Use of Smart Meters for Power Quality Monitoring in Emerging Networks
    Albu, Mihaela M.
    Sanduleac, Mihai
    Stanescu, Carmen
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2017, 8 (01) : 485 - 492
  • [4] Harmonic computation technique suitable for active power filters
    Alejandro Gonzalez, Sergio
    Garcia-Retegui, Rogelio
    Benedetti, Mario
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2007, 54 (05) : 2791 - 2796
  • [5] Andrews D, 2014, IEEE MICRO, V34, P55
  • [6] [Anonymous], 2010, IEEE Std.1044-2009, P1, DOI [DOI 10.1109/IEEESTD.2010.5439063, DOI 10.1109/IEEESTD.2010.5553440]
  • [7] [Anonymous], 2015, POWER SYSTEMS SIGNAL
  • [8] Arenas A, 2017, IND RELAT CONF MAN, P1, DOI 10.1007/978-3-319-66393-7
  • [9] Artale G, 2018, IEEE INT WORKS APPL, P64
  • [10] Berrisford AJ, 2015, IEEE IMTC P, P830, DOI 10.1109/I2MTC.2015.7151376