Indicator Analysis of Partial Discharges Measured Using Various Methods in Paper-Oil Insulation

被引:24
作者
Boczar, Tomasz [1 ]
Cichon, Andrzej [1 ]
Wotzka, Daria [1 ]
Kunicki, Michal [1 ]
Koziol, Michal [1 ]
机构
[1] Opole Univ Technol, Fac Elect Engn Automat Control & Comp Sci, Proszkowska 76, PL-45758 Opole, Poland
关键词
partial discharges; fault diagnosis; oil insulation; power transformer; insulation testing; signal processing; POWER TRANSFORMERS; LOCATION; SIGNALS; UHF; IDENTIFICATION; LOCALIZATION; PD; SENSOR;
D O I
10.1109/TDEI.2016.005972
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Results of a comparative analysis of two non-dimensional coefficients, calculated based on signals emitted by partial discharges (PD) are presented in the paper. The PD were generated using setups for modeling of three basic types of PD sources, which can occur in paper-oil insulation in power transformers. The following measuring methods were considered: electrical, ultra-high frequency, acoustic emission, and optical spectrophotometry. All measurements, for each of the PD-source configuration using the various methods, were conducted simultaneously in a laboratory under same measurement conditions. Based on the gathered results it was stated that it is possible to recognize the partial discharges form based on the non-dimensional coefficients, which differ in value for all of the considered methods except for the acoustic emission. The main contribution of the research performed lies in the simplicity of the applied signal processing procedure, which can be adopted to a device or system for diagnosis of partial discharges occurring in paper-oil insulation.
引用
收藏
页码:120 / 128
页数:9
相关论文
共 38 条
[1]  
[Anonymous], 2015, IEC Standard 60270, V3
[2]  
Badent R, 2008, IEEE ANN REPORT C EI, V2, P452
[3]   Statistical Analysis of Online Ultrahigh-Frequency Partial-Discharge Measurement of Power Transformers [J].
Beltle, Michael ;
Mueller, Andreas ;
Tenbohlen, Stefan .
IEEE ELECTRICAL INSULATION MAGAZINE, 2012, 28 (06) :17-22
[4]   A Methodology for Identification and Localization of Partial Discharge Sources using Optical Sensors [J].
Biswas, S. ;
Koley, C. ;
Chatterjee, B. ;
Chakravorti, S. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (01) :18-28
[5]  
Boczar T., 2003, Archives of Acoustics, V28, P161
[6]   Application Possibilities of Artificial Neural Networks for Recognizing Partial Discharges Measured by the Acoustic Emission Method [J].
Boczar, T. ;
Borucki, S. ;
Cichon, A. ;
Zmarzly, D. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2009, 16 (01) :214-223
[7]   Identification of a specific type of PD from acoustic emission frequency spectra [J].
Boczar, T .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2001, 8 (04) :598-606
[8]   Diagnostic Expert System of Transformer Insulation Systems using the Acoustic Emission Method [J].
Boczar, Tomasz ;
Cichon, Andrzej ;
Borucki, Sebastian .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (02) :854-865
[9]   Modeling of Acoustic Emission Signals Generated in On Load Tap Changer [J].
Cichon, A. ;
Borucki, S. ;
Wotzka, D. .
ACTA PHYSICA POLONICA A, 2014, 125 (06) :1396-1399
[10]   Characteristic of Acoustic Signals Generated by Operation of On Load Tap Changers [J].
Cichon, A. ;
Fracz, P. ;
Zmarzly, D. .
ACTA PHYSICA POLONICA A, 2011, 120 (04) :585-588