Study on Overvoltage and Insulation Coordination of Grounding Pole Line for ±800kV UHVDC System

被引:0
|
作者
Xia Chao [1 ]
Chen Xiujuan [1 ]
Shi Weidong [1 ]
Liu Fan [2 ]
Xie Shijun [2 ]
机构
[1] China Elect Power Res Inst, Beijing 100192, Peoples R China
[2] State Grid Sichuan Elect Power Res Inst, Chengdu 610041, Sichuan, Peoples R China
关键词
UHVDC; grounding pole line; internal overvoltage; external insulation configuration;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The grounding pole line is an important equipment of the UHVDC transmission system. Due to the low steady state voltage of the grounding pole line during the normal operation, the grounding pole line adopts the external insulation of the 35kV AC line. However, 110kV voltage grade is used mostly for tower of the grounding pole. So the external insulation is lower. When the DC system runs out of balance, there will be overvoltage on the grounding pole line, which may cause the external insulation to be broken down. The "7.13" grounding line fault occurred in 2015 in +/- 800kV Bin-jin HVDC project. Due to the high voltage DC casing breaking down in Jinhua, the system turned directly into the unipolar operation. The overvoltage of the Yibin to Jinhua grounding line at the moment of the casing breakdown caused the insulation breakdown of the grounding electrode without causing action of the line arrester. Under the condition that the DC continuous flow can not be extinguished, the accident of grounding insulator, ground wire and conductor burning has occurred. The occurrence of "7.13" accident has exposed the overvoltage and insulation coordination design defects of the grounding electrode circuit of the HVDC system. In this paper, the "7.13" fault of +/- 800kV Yibin to Jinhua DC project was taken as the analysis object. The simulation model was established by using the power system analysis software, MATLAB Sim Power System. The internal overvoltage characteristics and distribution of the grounding circuit of the UHVDC system were analyzed. The grounding line internal overvoltage level was calculated. Analysis showed that the overvoltage inside the UHV grounding circuit was depended on grounding line length, system operation mode, outgoing arrester parameters. To inspect the grounding electrode line of the converter station, the closer the grounding position of the high voltage pole was to the inspected converter station, the higher the overvoltage of the line of the grounding electrode. For the ground electrode line overvoltage caused by the high voltage pole line grounding, it showed a gradual downward trend from the converter station to the grounding pole on the grounding electrode line. The maximum overvoltage on the grounding electrode line is often caused by grounding fault on the high voltage side when the DC system was full power. Such overvoltage is the control value for the external insulation operation of the grounding electrode line. Based on calculation results of overvoltage, the appropriate insulation configuration adjustment scheme for grounding electrode line was given. After the "7.13" fault, the SGCC made a unified adjustment for external insulation configuration of the UHVDC grounding electrode lines. Number of insulator strings on the grounding electrode line has been increased to 5 or 6 pieces from 3 or 4 pieces. Distance of the insulator parallel gap was increased to 68cm from 20cm. Thus the problem was avoided that the MOA on the grounding conductor outlet could not protect the external insulation. The conclusion is of great significance to guide the external insulation design, fault analysis and operation and maintenance of the DC grounding line.
引用
收藏
页码:2433 / 2439
页数:7
相关论文
共 50 条
  • [1] Insulation coordination for ±800kV UHVDC converter stations
    Beijing Wanglian HVDC Engineering Technology Co., Ltd, Beijing 100005, China
    Gaodianya Jishu, 2006, 9 (75-79):
  • [2] Insulation Coordination Optimization Study for ±800kV UHVDC Project with Increased Transmission Capacity
    Zhang Cuixia
    Zhang Liuchun
    2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,
  • [3] Comparison of Insulation Coordination Between ±800kV and ±1100kV UHVDC Systems
    Wang, Dong-ju
    Zhou, Hao
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2015, 10 (04) : 1773 - 1779
  • [4] Comparison of insulation coordination between ±800kV and ±1100kV UHVDC systems
    College of Electrical Engineering, Zhejiang University, China
    J. Electr. Eng. Technol., 4 (1774-1780):
  • [5] Overvoltage and insulation coordination for ±1100 kV UHVDC converter station
    Zhou, H. (zhouhao_ee@zju.edu.cn), 2013, Science Press (39):
  • [6] Study on Overvoltage Mechanism and Influencing Factors of Converter Valves in ±800kV Multi-terminal UHVDC System
    Nie N.
    Wang L.
    Wang D.
    Nan J.
    Li Z.
    Chen X.
    Zhou H.
    Dianwang Jishu/Power System Technology, 2020, 44 (01): : 307 - 315
  • [7] Technical,and economic performance analysis on vertical grounding electrodes of ±800KV UHVDC
    Wang Jianwu
    Wen Xishan
    Lan Lei
    Li Jiayuan
    2006 INTERNATIONAL CONFERENCE ON POWER SYSTEMS TECHNOLOGY: POWERCON, VOLS 1- 6, 2006, : 1162 - +
  • [8] Study on stability of ±800kV UHVDC transmission project
    Deng, Xuehua
    Zhou, Renjun
    Zhang, Chenhao
    2007 CONFERENCE PROCEEDINGS IPEC, VOLS 1-3, 2007, : 625 - +
  • [9] Study on the key equipment's insulation level of ±800kV UHVDC power transmission project
    Lv Jinzhuang
    Li Licheng
    2007 IEEE POWER ENGINEERING SOCIETY CONFERENCE AND EXPOSITION IN AFRICA, VOLS 1 AND 2, 2007, : 536 - 539
  • [10] The study on the radio interference from ±800kV Yun Guang UHVDC transmission line
    Wan Baoquan
    Liu Dichen
    Wu Xiong
    Lu Yao
    2006 INTERNATIONAL CONFERENCE ON POWER SYSTEMS TECHNOLOGY: POWERCON, VOLS 1- 6, 2006, : 130 - +