Study on Auto-ignition Behavior of Lubricating Oil in a Cone Calorimeter

被引:7
作者
Siregar, Muhammad Andira Mulia [1 ]
Nugroho, Yulianto Sulistyo [1 ]
机构
[1] Univ Indonesia, Dept Mech Engn, Thermodynam Lab, Fire Safety Engn Res Grp, Depok 16424, Indonesia
来源
ADVANCES IN APPLIED MECHANICS AND MATERIALS | 2014年 / 493卷
关键词
auto-ignition; cone calorimeter; heat release rate; lubricating oil; optical density index;
D O I
10.4028/www.scientific.net/AMM.493.161
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
Auto-ignition behavior of lubricating oil is studied experimentally using a cone calorimeter. Based on its Material Safety Data Sheet (MSDS), the adopted lubricating oil has a flash point temperature of 228 degrees C, The measurement of auto-ignition behavior was carried at atmospheric pressure in range of temperature between 350 degrees C to 550 degrees C. In this work, the optical density of smoke resulting from the combustion process was measured at auto-ignition temperature. The result of this study shows that the auto-ignition behavior of lubricating oil is strongly depend on conditions of gas mixture, i.e. oil vapor, nitrogen, and oxygen mixtures. The lubricating oil started to ignite at irradiance temperature of cone heater at 500 degrees C with a measured heat flux value of 16,7 kW/m(2). At lower temperatures ignition of the mixture occured by piloted igniton sources. No ignition was observed at temperature less than 350 degrees C. At higher irradiance temperature and heat flux (550 degrees C and 21,1 kW/m2), auto-ignition occured at shorter time to ignition and producing higher value of smoke's optical density of 1 - 1.4 m(-1).
引用
收藏
页码:161 / 166
页数:6
相关论文
共 13 条
[1]  
[Anonymous], 2007, ACCIDENT STAT FIXED
[2]  
[Anonymous], 2004, E135404A ASTM INT
[3]  
Apriano T., 2012, THESIS U INDONESIA
[4]  
Babrauskas V., 2002, Heat Release Rates, The SFPE handbook of fire protection Engineering, V3rd
[5]  
Cote A.E, 2003, FIRE PROTECTION HDB, V19th ed.
[6]  
Det Norske Veritas, 2007, ENG ROOM FIR CAN BE
[7]  
Drysdale D, 2004, INTRO FIRE DYNAMICS, V2nd
[8]   ESTIMATION OF RATE OF HEAT RELEASE BY MEANS OF OXYGEN-CONSUMPTION MEASUREMENTS [J].
HUGGETT, C .
FIRE AND MATERIALS, 1980, 4 (02) :61-65
[9]   Auto-ignition of lubricating oil working at high pressures in a compressor for an air conditioner [J].
Kim, Chul Jin ;
Choi, Hyo Hyun ;
Sohn, Chae Hoon .
JOURNAL OF HAZARDOUS MATERIALS, 2011, 185 (01) :416-422
[10]   Using cone calorimeter data for the prediction of fire hazard [J].
Kuang-Chung, T ;
Drysdale, D .
FIRE SAFETY JOURNAL, 2002, 37 (07) :697-706