Fractional-order Proportional-integral-derivative-based Automatic Generation Control in Deregulated Power Systems

被引:41
作者
Chathoth, Ismayil [1 ]
Ramdas, Sreerama Kumar [2 ]
Krishnan, Sindhu Thiruthimana [1 ]
机构
[1] Natl Inst Technol, Dept Elect Engn, Calicut, Kerala, India
[2] King Abdulaziz Univ, Jeddah 21413, Saudi Arabia
关键词
automatic generation control; deregulated power systems; fractional calculus; fractional-order controller; fuzzy logic control; genetic algorithm; load frequency control; power system control; distribution company participation matrix; LOAD FREQUENCY CONTROLLER; GENETIC-ALGORITHM; ROBUST METHOD; AGC; OPTIMIZATION; DESIGN;
D O I
10.1080/15325008.2015.1072256
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this article, implementation of a fractional-order proportional-integral-derivative controller is proposed as supplementary automatic generation control of interconnected multi-area deregulated power systems that operates under the effects of bilateral contracts on the dynamics. The tuning of the fractional-order proportional-integral-derivative controller parameters is formulated as an optimization problem and solved by employing a genetic algorithm. The traditional automatic generation control loop incorporated with the concept of the distribution company participation matrix and fractional-order proportional-integral-derivative supplementary controller is simulated for different operating cases; a comparison among the conventional integral controller, hybrid fuzzy proportional-integral controller, genetic algorithm-tuned proportional-integral controller, and genetic algorithm-tuned proportional-integral-derivative controllers is presented. The simulation results show that the system employing a genetic algorithm-tuned fractional-order proportional-integral-derivative controller has better performance than the integer-order hybrid fuzzy proportional-integral, genetic algorithm-tuned proportional-integral, and genetic algorithm-tuned proportional-integral-derivative controllers in terms of settling time and overshoot.
引用
收藏
页码:1931 / 1945
页数:15
相关论文
共 34 条
[1]   Optimal AGC tuning with genetic algorithms [J].
AbdelMagid, YL ;
Dawoud, MM .
ELECTRIC POWER SYSTEMS RESEARCH, 1996, 38 (03) :231-238
[2]   Load following in a bilateral market with local controllers [J].
Abraham, Rajesh Joseph ;
Das, D. ;
Patra, Amit .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2011, 33 (10) :1648-1657
[3]   Design of load frequency controllers using genetic algorithm for two area interconnected hydro power system [J].
Aditya, SK ;
Das, D .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2003, 31 (01) :81-94
[4]  
ALOMOUSH MI, 2010, J ELECT ENG, V91, P357, DOI DOI 10.1007/S00202-009-0145-7
[5]   Automatic generation control in a deregulated power system [J].
Bakken, BH ;
Grande, OS .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1998, 13 (04) :1401-1406
[6]   Optimized multi area AGC simulation in restructured power systems [J].
Bhatt, Praghnesh ;
Roy, Ranjit ;
Ghoshal, S. P. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2010, 32 (04) :311-322
[7]   Load frequency control using genetic-algorithm based fuzzy gain scheduling of PI controllers [J].
Chang, CS ;
Fu, WH ;
Wen, FS .
ELECTRIC MACHINES AND POWER SYSTEMS, 1998, 26 (01) :39-52
[8]   Load frequency control issues in power system operations after deregulation - Response [J].
Christie, RD ;
Bose, A .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (03) :1199-1200
[9]   AGC of a multi-area thermal system under deregulated environment using a non-integer controller [J].
Debbarma, Sanjoy ;
Saikia, Lalit Chandra ;
Sinha, Nidul .
ELECTRIC POWER SYSTEMS RESEARCH, 2013, 95 :175-183
[10]   GA application to optimization of AGC in three-area power system after deregulation [J].
Demiroren, A. ;
Zeynelgil, H. L. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2007, 29 (03) :230-240