Power Comparator Based On-Site Calibration of Isolating Current Transformers

被引:2
作者
Mohns, Enrico [1 ]
Latzel, Hans-Georg [1 ]
Wittig, Cornelia [1 ]
机构
[1] PTB Braunschweig Germany, D-38116 Braunschweig, Germany
来源
MAPAN-JOURNAL OF METROLOGY SOCIETY OF INDIA | 2009年 / 24卷 / 01期
关键词
Measurement Uncertainty; Test Current; Magnetization Impedance; Ratio Error; Current Path;
D O I
10.1007/s12647-009-0008-8
中图分类号
TH7 [仪器、仪表];
学科分类号
0804 ; 080401 ; 081102 ;
摘要
A portable system for on-site calibrations of isolating current transformers in stationary energy meter test systems is described. The uncertainties of the calibration system are in the order of 0.005 % for the ratio error and 0.01 crad for the phase displacement of the current transformer at power frequencies. The power comparator based measurements can be done at test currents from 50 mA to 120 A.
引用
收藏
页码:67 / 72
页数:6
相关论文
共 3 条
  • [1] BACHMAIR H, 1977, UNTERSUCHUNG FEHLER
  • [2] MOORE WJM, 1988, IEEE ELECT MEASURMEN, V4