MAPAN-JOURNAL OF METROLOGY SOCIETY OF INDIA
|
2009年
/
24卷
/
01期
关键词:
Measurement Uncertainty;
Test Current;
Magnetization Impedance;
Ratio Error;
Current Path;
D O I:
10.1007/s12647-009-0008-8
中图分类号:
TH7 [仪器、仪表];
学科分类号:
0804 ;
080401 ;
081102 ;
摘要:
A portable system for on-site calibrations of isolating current transformers in stationary energy meter test systems is described. The uncertainties of the calibration system are in the order of 0.005 % for the ratio error and 0.01 crad for the phase displacement of the current transformer at power frequencies. The power comparator based measurements can be done at test currents from 50 mA to 120 A.