Influence of mechanical ventilation system on indoor carbon dioxide and particulate matter concentration

被引:40
作者
Yu, Conson K. H. [1 ]
Li, Min [2 ]
Chan, Vincent [3 ]
Lai, Alvin C. K. [1 ]
机构
[1] City Univ Hong Kong, Dept Civil & Architectural Engn, Kowloon, Hong Kong, Peoples R China
[2] Cent S Univ, Sch Energy Sci & Engn, Changsha 410083, Hunan, Peoples R China
[3] Nanyang Technol Univ, Sch Chem & Biomed Engn, Singapore 639798, Singapore
关键词
CO2-based demand-controlled; IAQ; Particulate matter; State-space model; Ventilation; DEMAND-CONTROLLED VENTILATION; PARTICLE NUMBER; FILTRATION; EXPOSURE; PM2.5; MODEL;
D O I
10.1016/j.buildenv.2014.03.004
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Common ventilation strategies may fail to maintain indoor air quality when atmosphere is heavily polluted by particulate matter. This paper evaluates the performances of common constant air volume (CAV) system and variable air volume (VAV) system when carbon dioxide and particles are significantly present in outdoor environment. Major system parameters including filter efficiency, occupancy number, ventilation air rate, and outdoor particle concentration are thoroughly examined. Firstly, a full-scale chamber experiment is performed to investigate the dynamics of CO2 and airborne particles under steady and non-steady scenarios. The result is further validated with a previously-developed state-space model. Secondly, an exhaustive case study is conducted using an established mathematical model. In order to reduce CO2 concentration, both CAV and CO2-based demand-controlled VAV may cause an undesirable increase in particle concentration when outdoor air is heavily polluted by particles. This dilemma requires further studies on the optimization of ventilation schemes. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:73 / 80
页数:8
相关论文
共 37 条
[1]  
American Society of Heating, 2010, 6212010 ANSIASHRAE
[2]  
American Society of Heating Refrigerating and Air-Conditioning Engineers, 2009, ASHRAE HDB FUND
[3]  
[Anonymous], GUID IND AIR QUAL CE
[4]  
[Anonymous], 2011, AIR QUAL HONG KONG
[5]  
[Anonymous], 2006, Air Quality Guidelines: Global Update 2005: Particulate Matter, Ozone, Nitrogen Dioxide, and Sulfur Dioxide
[6]   Development of a dual-mode demand control ventilation strategy for indoor air quality control and energy saving [J].
Chao, CYH ;
Hu, JS .
BUILDING AND ENVIRONMENT, 2004, 39 (04) :385-397
[7]   Airborne particulate matter and human health: A review [J].
Davidson, CI ;
Phalen, RF ;
Solomon, PA .
AEROSOL SCIENCE AND TECHNOLOGY, 2005, 39 (08) :737-749
[8]   Relationships between indoor and outdoor contaminants in mechanically ventilated buildings [J].
Ekberg, LE .
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 1996, 6 (01) :41-47
[9]   Source strengths for indoor human activities that resuspend particulate matter [J].
Ferro, AR ;
Kopperud, RJ ;
Hildemann, LM .
ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2004, 38 (06) :1759-1764
[10]   Sensor-based demand-controlled ventilation: a review [J].
Fisk, WJ ;
De Almeida, AT .
ENERGY AND BUILDINGS, 1998, 29 (01) :35-45