Ventilation system type, classroom environmental quality and pupils' perceptions and symptoms

被引:110
作者
Gao, Jie [1 ,2 ]
Wargocki, Pawel [1 ]
Wang, Yi [2 ]
机构
[1] Tech Univ Denmark, Int Ctr Indoor Environm & Energy, Dept Civil Engn, DK-2800 Lyngby, Denmark
[2] Xian Univ Architecture & Technol, Sch Environm & Municipal Engn, Xian, Peoples R China
基金
中国国家自然科学基金;
关键词
Ventilation system type; Temperature; Carbon dioxide; Window opening; Perception and symptom; INDOOR AIR-QUALITY; CO2; CONCENTRATIONS; ASSOCIATION; HEALTH; COMFORT; SCHOOLS; RATES; FLOW;
D O I
10.1016/j.buildenv.2014.01.015
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The present study investigated indoor climate and window opening behaviour by pupils, as well as their perceptions and symptoms in classrooms with different types of ventilation systems. Four classrooms were selected in the same school in suburban Denmark. Classroom ventilation was achieved either by manually operable windows, or by automatically operable windows with and without an exhaust fan in operation, or by a balanced mechanical ventilation system. Indoor air temperature, relative humidity, carbon dioxide (CO2) concentration and window opening were continuously monitored for one month in non-heating and heating seasons; CO2 concentration was used to estimate average classroom ventilation rates. At the end of each measuring period, the pupils were asked to report their perceptions of the indoor environment and their acute health-related symptoms. The classroom in which ventilation was achieved by manually operable windows had the highest air temperatures and CO2 concentrations during both non-heating and heating season; the estimated average air-change rate was lowest in this classroom. The classroom with mechanical ventilation had the highest estimated average air-change rate. Windows were frequently opened in all four classrooms in the non-heating season but very seldom in the heating season. Automatic operation of the windows had a marked effect on CO2 concentration and classroom temperature in the heating season. Perceptions of the indoor environment were more positive in the classroom that was ventilated by automatically operable windows with an exhaust fan in operation: fewer symptoms were reported in this classroom compared with classrooms with other systems. Present results and approach can be used as the basis for rational selection of systems that ensure adequate classroom ventilation. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:46 / 57
页数:12
相关论文
共 43 条
[1]  
[Anonymous], BUILDING ENV
[2]   Sensory pollution from bag filters, carbon filters and combinations [J].
Bekoe, G. ;
Clausen, G. ;
Weschler, C. J. .
INDOOR AIR, 2008, 18 (01) :27-36
[3]   European indoor air quality audit project in 56 office buildings [J].
Bluyssen, PM ;
Fernandes, ED ;
Groes, L ;
Clausen, G ;
Fanger, PO ;
Valbjorn, O ;
Bernhard, CA ;
Roulet, CA .
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 1996, 6 (04) :221-238
[4]  
Brelih N, 2012, REHVA J, P24
[5]  
Coley D. A., 2002, International Journal of Ventilation, V1, P45, DOI DOI 10.1080/14733315.2002.11683621
[6]   Indoor air quality, ventilation and health symptoms in schools: an analysis of existing information [J].
Daisey, JM ;
Angell, WJ ;
Apte, MG .
INDOOR AIR, 2003, 13 (01) :53-64
[7]  
Di Perna C, 2011, INT J VENT, V10, P61
[8]   Ventilation in European dwellings: A review [J].
Dimitroulopoulou, C. .
BUILDING AND ENVIRONMENT, 2012, 47 :109-125
[9]   Occupants' window opening behaviour: A literature review of factors influencing occupant behaviour and models [J].
Fabi, Valentina ;
Andersen, Rune Vinther ;
Corgnati, Stefano ;
Olesen, Bjarne W. .
BUILDING AND ENVIRONMENT, 2012, 58 :188-198
[10]   Impact of temperature and humidity on perception of indoor air quality during immediate and longer whole-body exposures [J].
Fang, L ;
Clausen, G ;
Fanger, PO .
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 1998, 8 (04) :276-284