Model-based automatic tuning of a filtration control system for submerged anaerobic membrane bioreactors (AnMBR)

被引:24
作者
Robles, A. [1 ]
Ruano, M. V. [1 ]
Ribes, J. [1 ]
Seco, A. [1 ]
Ferrer, J. [2 ]
机构
[1] Univ Valencia, Escola Tecn Super Engn, Dept Engn Quim, E-46100 Valencia, Spain
[2] Univ Politecn Valencia, IIAMA, Inst Univ Invest Engn Aigua & Medi Ambient, Valencia 46022, Spain
关键词
Industrial-scale membranes; Model-based control; Monte Carlo procedure; Morris screening method; Submerged anaerobic MRR (AnMBR); GLOBAL SENSITIVITY-ANALYSIS; CONTROL STRATEGIES; WASTE; REMOVAL; OPTIMIZATION; SIMULATION; NITROGEN; DESIGN;
D O I
10.1016/j.memsci.2014.04.012
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
This paper describes a model-based method to optimise filtration in submerged AnMBRs. The method is applied to an advanced knowledge-based control system and considers three statistical methods: (1) sensitivity analysis (Morris screening method) to identify an input subset for the advanced controller; (2) Monte Carlo method (trajectory-based random sampling) to find suitable initial values for the control inputs; and (3) optimisation algorithm (performing as a supervisory controller) to re-calibrate these control inputs in order to minimise plant operating costs. The model-based supervisory controller proposed allowed filtration to be optimised with low computational demands (about 5 min). Energy savings of up to 25% were achieved when using gas sparging to scour membranes. Downtime for physical cleaning was about 2.4% of operating time The operating cost of the AnMBR system after implementing the proposed supervisory controller was about 0.045/m(3), 53.3% of which were energy costs. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:14 / 26
页数:13
相关论文
共 47 条
[1]  
Apha AW., 1995, Standard Methods for the Examination of Water and Wastewater, V19th, DOI DOI 10.2105/AJPH.56.4.684-A
[2]   Automatic tuning and adaptation for pid controllers - survey [J].
Astrom, K.J. ;
Hagglund, T. ;
Hang, C.C. ;
Ho, W.K. .
Control Engineering Practice, 1993, 1 (04) :699-714
[3]   Multi-criteria analysis of wastewater treatment plant design and control scenarios under uncertainty [J].
Benedetti, L. ;
De Baets, B. ;
Nopens, I. ;
Vanrolleghem, P. A. .
ENVIRONMENTAL MODELLING & SOFTWARE, 2010, 25 (05) :616-621
[4]  
Beraud B, 2008, COMPUT-AIDED CHEM EN, V25, P539
[5]  
Brown TR, 2000, HYDROCARB PROCESS, V79, P93
[6]   Run-to-run control of membrane filtration processes [J].
Busch, Jan ;
Cruse, Andreas ;
Marquardt, Wolfgang .
AICHE JOURNAL, 2007, 53 (09) :2316-2328
[7]   An effective screening design for sensitivity analysis of large models [J].
Campolongo, Francesca ;
Cariboni, Jessica ;
Saltelli, Andrea .
ENVIRONMENTAL MODELLING & SOFTWARE, 2007, 22 (10) :1509-1518
[8]   An interior trust region approach for nonlinear minimization subject to bounds [J].
Coleman, TF ;
Li, YY .
SIAM JOURNAL ON OPTIMIZATION, 1996, 6 (02) :418-445
[9]  
Copp J.B., 2002, The COST simulation benchmark-Description and simulator manual
[10]  
Copp J. B., 1999, CHEM ENG DESIGN PRIN