Fire tests on full-scale steel portal frames against progressive collapse

被引:54
作者
Lou, Guobiao [1 ,2 ]
Wang, Chenghao [2 ]
Jiang, Jian [2 ,3 ]
Jiang, Yaqiang [4 ]
Wang, Liangwei [4 ]
Li, Guo-Qiang [1 ,2 ]
机构
[1] Tongji Univ, State Key Lab Disaster Reduct Civil Engn, Shanghai 200092, Peoples R China
[2] Tongji Univ, Coll Civil Engn, Shanghai 200092, Peoples R China
[3] Natl Inst Stand & Technol, Engn Lab, Gaithersburg, MD 20899 USA
[4] Minist Publ Secur, Sichuan Fire Res Inst, Chengdu 610036, Sichuan, Peoples R China
基金
中国国家自然科学基金;
关键词
Fire test; Steel portal frame; Progressive collapse; Gas temperature; Collapse mode; Numerical simulation; COMPOSITE FLOORS; ELEVATED-TEMPERATURES; COMPARTMENT FIRES; CONCRETE SLABS; LOCALIZED FIRE; PART; BEHAVIOR; DESIGN; CONNECTIONS; MECHANISMS;
D O I
10.1016/j.jcsr.2018.02.024
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper presents experimental investigations on the collapse behavior of a full-scale 36 m x 12 m steel portal frame exposed to natural fires. Extensive thermal and structural responses of the frame are measured and presented. The frame collapses after 15-min fire exposure with a critical temperature of about 1100 degrees C in the heated column. The measured gas temperature history has a short growth period of 3 min, and reaches its peak temperature of 1100 degrees C within 8 min (400 degrees C higher than standard fire). It is found that a two-zone model can be assumed with uniform temperature distribution in the lower and upper half region, respectively. The temperature gap of these two zones reaches 200 degrees C. The gas temperature at top region decreases due to the deformation-induced opening of roof and fire walls. The surface facing the environment has higher gas temperatures than that inside the fire compartment (more than 200 degrees C). The temperature of rafters beyond the fire compartment reaches 700 degrees C due to the spread hot smoke. Outward bending of the external unexposed column and pulling out of corner column base are observed, which should be prevented in practical design to mitigate fire spread to adjacent buildings and ensure life safety of fire fighters. Numerical simulation is conducted and compared to experimental results which can be used for calibrating numerical models. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:137 / 152
页数:16
相关论文
共 45 条
[1]   Lateral displacement and collapse of single-story steel frames in uncontrolled fires [J].
Ali, HM ;
Senseny, PE ;
Alpert, RL .
ENGINEERING STRUCTURES, 2004, 26 (05) :593-607
[2]   Valencia bridge fire tests: Experimental study of a composite bridge under fire [J].
Alos-Moya, Jose ;
Paya-Zaforteza, Ignacio ;
Hospitaler, Antonio ;
Rinaudo, Paula .
JOURNAL OF CONSTRUCTIONAL STEEL RESEARCH, 2017, 138 :538-554
[3]  
[Anonymous], 1990, BS5950 8
[4]  
[Anonymous], 2005, Eurocode 3: Design of Steel Structures, Part 1-2: General Rules - Structural Fire Design
[5]  
[Anonymous], BRIT STEEL TECHNICAL
[6]  
[Anonymous], 1999, ISO 834
[7]  
[Anonymous], 2002, 02SG5181 CHINA BUILD
[8]  
ASCE, 2005, ASCE Standard No. ASCE/SEI 7
[9]  
Balogh T., 2017, PERIOD POLYTECH, V61, P1
[10]  
Bong M.W., 2007, P PAC STRUCT STEEL C