An Acoustic Emission Method for On-line Monitoring the Contamination-causing Flashover of Insulator

被引:0
作者
Pei, C. M. [1 ]
Shu, N. Q. [1 ]
Li, L. [1 ]
Wang, D. [1 ]
Li, Z. P. [1 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Peoples R China
来源
ICEMS 2008: PROCEEDINGS OF THE 11TH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1- 8 | 2008年
关键词
acoustic emission (AE); flashover; insulator; monitoring; partial charge (PD);
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents an acoustic emission (AE) monitoring method. When a partial discharge occurs, there is an instantaneous release of energy, some of which is emitted as acoustic energy. The pollution severities of insulators in-service can be monitored and accordingly threaten to the insulation of power grid is evaluated by detecting the sound signals. To prove this AE monitoring method, artificial contaminations experiments are carried out. The essential information about the relationship of AE signal and PD are obtained in different moments of the whole process of flashover. The studied method is a new way of AE technique in monitoring and characterizing defects of electrical power equipments in-service.
引用
收藏
页码:817 / 822
页数:6
相关论文
共 9 条
[1]  
ABDELSALAM M, 2001, IND APPL C REC 2001, V4, P2541, DOI DOI 10.1109/IAS.2001.955978
[2]  
Cheng Yang-chun, 2000, Proceedings of the CSEE, V20, P54
[3]   AC CLEAN FOG TESTS ON NON-CERAMIC INSULATING MATERIALS AND A COMPARISON WITH PORCELAIN [J].
DELAO, A ;
GORUR, RS ;
CHANG, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (04) :2000-2008
[4]   On-line leakage current monitoring of 400 kV insulator strings in polluted areas [J].
FierroChavez, JL ;
RamirezVazquez, I ;
MontoyaTena, G .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1996, 143 (06) :560-564
[5]  
Lundgaard L. E., 1992, IEEE Electrical Insulation Magazine, V8, P34, DOI 10.1109/57.156943
[6]  
Lundgaard L. E., 1992, IEEE Electrical Insulation Magazine, V8, P25, DOI 10.1109/57.145095
[7]  
Wong KL, 2002, POWERCON 2002: INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS 1-4, PROCEEDINGS, P1859, DOI 10.1109/ICPST.2002.1067854
[8]  
ZHANG CH, 2003, IEEE T DIELECTRICS E, V10
[9]  
1994, INSULATION POLLUTION