Melting and breaking characteristics of OPGW strands by lightning

被引:29
作者
Goda, Y [1 ]
Yokoyama, S
Watanabe, S
Kawano, T
Kanda, S
机构
[1] CRIEPI, Yokosuka Res Lab, Yokosuka, Kanagawa 2400196, Japan
[2] CRIEPI, Komae Res Lab, Tokyo, Japan
[3] Shikoku Elect Power Co Inc, Kagawa, Japan
关键词
arc discharges; lightning; optical fiber cables; transmission lines;
D O I
10.1109/TPWRD.2004.832410
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Some strands were melted and broken in a 140 mm 2 OPGW (composite fiber-optic ground wire) in a 187 kV transmission line. It was assumed that this was caused by a lightning strike. DC are tests simulating lightning strikes were carried out, and the melting and breaking characteristics of OPGW strands were obtained. The electric charge of the lightning strike that damaged the OPGW was estimated from the number of strands broken by the DC arc. In this paper, the DC are test results, and the test conditions required to simulate a powerful lightning strike are described.
引用
收藏
页码:1734 / 1739
页数:6
相关论文
共 11 条
  • [1] BOHME B, 1998, P ICLP, P571
  • [2] *CRIEPI, 1988, T10 CRIEPI
  • [3] Fukagawa H, 1989, W04 CRIEPI
  • [4] GODA Y, 2000, W99520 CRIEPI
  • [5] *IEC, 1999, 6079441 IEC
  • [6] KITO Y, 1988, T IEE JAPAN B, V108, P577
  • [7] Shibuya M., 1993, Transactions of the Institute of Electrical Engineers of Japan, Part B, V113-B, P327
  • [8] SHIBUYA M, 1986, I ELECT ENG JPN NATL
  • [9] SUNABE K, 1984, 183517 CRIEPI
  • [10] SUNABE K, 1999, W14 CRIEPI