A full-scale field study for evaluation of simple analytical models of cross ventilation and single-sided ventilation

被引:21
作者
Fan, S. [1 ]
Wykes, M. S. Davies [2 ]
Lin, W. E. [3 ]
Jones, R. L. [1 ]
Robins, A. G. [3 ]
Linden, P. F. [4 ]
机构
[1] Univ Cambridge, Dept Chem, Cambridge CB2 1EW, England
[2] Univ Cambridge, Dept Engn, Cambridge CB2 1PZ, England
[3] Univ Surrey, Dept Mech Engn Sci, Guildford GU2 7XH, Surrey, England
[4] Univ Cambridge, Dept Appl Math & Theoret Phys, Cambridge CB3 0WA, England
基金
英国工程与自然科学研究理事会;
关键词
Natural ventilation models; Tracer gas technique; Local wind speed; Pressure coefficient; Wind tunnel experiments; NATURAL VENTILATION; TRACER-GAS; NUMERICAL-SIMULATION; WIND; PRESSURE; BUILDINGS; IMPACT; DRIVEN; STACK; FLOW;
D O I
10.1016/j.buildenv.2020.107386
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this study, we evaluated several simple natural ventilation models of cross ventilation and single-sided ventilation with data measured in a full-scale field study in London. In the field study, the ventilation rate in a naturally ventilated office was measured using a tracer gas technique with CO2. Internal temperatures were measured using a vertical temperature array. The external temperature, wind speed and direction were measured at a nearby weather station. In addition, a 1:200 scale model of the urban area within 300 m of the test room was built in a wind tunnel to measure the pressure coefficients. The ventilation models were evaluated with input data from two sources. Wind data from a nearby airport and pressure coefficients from the literature were used, as is common practice. Alternatively, wind data measured at the local weather station and the pressure coefficients measured from wind tunnel experiments were used. The results showed that, regardless of the input data sources, the cross-ventilation model in general gives reasonable predictions. For single-sided ventilation, several empirical models were evaluated and poor predictions were obtained using the models. We discuss ways in which models of natural ventilation might be improved in the future.
引用
收藏
页数:11
相关论文
共 43 条
  • [1] The influence of single-sided ventilation towards the indoor thermal performance of high-rise residential building: A field study
    Aflaki, Ardalan
    Mahyuddin, Norhayati
    Baharum, Mohamad Rizal
    [J]. ENERGY AND BUILDINGS, 2016, 126 : 146 - 158
  • [2] Batterman S., 2017, J ENV RES PUBL HLTH, V14, DOI DOI 10.3390/IIERPH14020145
  • [3] Bohnenstengel S.I., 2011, Q J R METEOROL SOC, DOI [10.1002/QI.855, DOI 10.1002/QI.855]
  • [4] Numerical simulation of single-sided ventilation using RANS and LES and comparison with full-scale experiments
    Caciolo, Marcello
    Stabat, Pascal
    Marchio, Dominique
    [J]. BUILDING AND ENVIRONMENT, 2012, 50 : 202 - 213
  • [5] Full scale experimental study of single-sided ventilation: Analysis of stack and wind effects
    Caciolo, Marcello
    Stabat, Pascal
    Marchio, Dominique
    [J]. ENERGY AND BUILDINGS, 2011, 43 (07) : 1765 - 1773
  • [6] Coley D. A., 2002, International Journal of Ventilation, V1, P45, DOI DOI 10.1080/14733315.2002.11683621
  • [7] CO2 tracer gas concentration decay method for measuring air change rate
    Cui, Shuqing
    Cohen, Michael
    Stabat, Pascal
    Marchio, Dominique
    [J]. BUILDING AND ENVIRONMENT, 2015, 84 : 162 - 169
  • [8] da Graca G. Carrilho, 2016, BUILD ENVIRON, DOI [10.1016/j.buildenv.2016.08.007, DOI 10.1016/J.BUILDENV.2016]
  • [9] Etheridge D.W., 2004, International Journal of Ventilation, V2, P325, DOI 10.1080/14733315.2004.11683676