Energy Balancing Improvement of Modular Multilevel Converters Under Unbalanced Grid Conditions

被引:69
作者
Leon, Andres E. [1 ]
Amodeo, Santiago J. [2 ,3 ]
机构
[1] Univ Nacl Sur, Inst Invest Ingn Elect Alfredo Desages, Bahia Blanca, Buenos Aires, Argentina
[2] ElectroAMSA Co, Bahia Blanca, Buenos Aires, Argentina
[3] Univ Nacl Sur, Dept Elect & Comp Engn, Bahia Blanca, Buenos Aires, Argentina
关键词
Capacitor voltage balancing; feed-forward control; modular multilevel converter (MMC); unbalanced operation; voltage-source converter (VSC)-based high-voltage direct current; (HVdc) transmission systems; MMC-HVDC; CONTROL STRATEGY; CONTROL-SYSTEM; MODELS; PERFORMANCE;
D O I
10.1109/TPEL.2016.2621000
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a feedback/feed-forward control strategy to improve the voltage balancing of modular multilevel converters (MMCs) under unbalanced grid conditions. The inclusion of a feed-forward compensation improves the disturbance rejection capability against asymmetrical faults and sudden voltage imbalances in the ac grid. The floating capacitor voltages of the MMC are controlled in two stages. The first one equally distributes the voltages in each arm, and the second one balances the energy among the six arms. This last control stage is also divided into the called horizontal and vertical balancing. Based on a detailed analysis of the power terms disturbing the MMC arm energies, the control strategy is tailored to improve the voltage transient response by adding feed-forward terms to both horizontal and vertical balancing controls. In addition, various approaches to manage the MMC under unbalanced grid conditions are compared regarding several aspects, such as capacitor voltage ripple, balancing performance, and negative-sequence current injection. Advantages and disadvantages of both the proposed and the conventional energy-based control schemes are also studied, showing that the voltage control performance can be improved by enhancing the existing MMC control systems.
引用
收藏
页码:6628 / 6637
页数:10
相关论文
共 47 条
[21]   Software Sensor-Based STATCOM Control Under Unbalanced Conditions [J].
Leon, Andres E. ;
Manuel Mauricio, Juan ;
Solsona, Jorge A. ;
Gomez-Exposito, Antonio .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) :1623-1632
[22]   Circulating Current Suppressing Strategy for MMC-HVDC Based on Nonideal Proportional Resonant Controllers Under Unbalanced Grid Conditions [J].
Li, Shaohua ;
Wang, Xiuli ;
Yao, Zhiqing ;
Li, Tai ;
Peng, Zhong .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2015, 30 (01) :387-397
[23]   The Impact of Voltage-Balancing Control on Switching Frequency of the Modular Multilevel Converter [J].
Li, Yalong ;
Jones, Edward A. ;
Wang, Fei .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2016, 31 (04) :2829-2839
[24]  
Liang Y., 2016, IEEE T POWE IN PRESS
[25]   Grouping-Sorting-Optimized Model Predictive Control for Modular Multilevel Converter With Reduced Computational Load [J].
Liu, Pu ;
Wang, Yue ;
Cong, Wulong ;
Lei, Wanjun .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2016, 31 (03) :1896-1907
[26]  
Lizana R, 2012, IEEE IND ELEC, P4935, DOI 10.1109/IECON.2012.6389573
[27]   A Simplified Nearest Level Control (NLC) Voltage Balancing Method for Modular Multilevel Converter (MMC) [J].
Meshram, Prafullachandra M. ;
Borghate, Vijay B. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2015, 30 (01) :450-462
[28]   Model Predictive Control With a Reduced Number of Considered States in a Modular Multilevel Converter for HVDC System [J].
Moon, Ji-Woo ;
Gwon, Jin-Su ;
Park, Jung-Woo ;
Kang, Dae-Wook ;
Kim, Jang-Mok .
IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (02) :608-617
[29]   A Control Method of HVDC-Modular Multilevel Converter Based on Arm Current Under the Unbalanced Voltage Condition [J].
Moon, Ji-Woo ;
Park, Jung-Woo ;
Kang, Dae-Wook ;
Kim, Jang-Mok .
IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (02) :529-536
[30]   Circulating Current Control in MMC Under the Unbalanced Voltage [J].
Moon, Ji-Woo ;
Kim, Chun-Sung ;
Park, Jung-Woo ;
Kang, Dae-Wook ;
Kim, Jang-Mok .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (03) :1952-1959