Dynamic Simulation and Operating Characteristics of Ground-Coupled Heat Pump with Solar Seasonal Heat Storage System

被引:8
|
作者
Lyu, Chao [1 ]
Leong, Wey H. [2 ]
Zheng, Maoyu [3 ]
Jiang, Ping [1 ]
Yu, Feng [1 ]
Liu, Yueqin [4 ,5 ]
机构
[1] Zhejiang Sci Tech Univ, Sch Civil Engn & Architecture, 928 Second Ave,Xiasha Higher Educ Zone, Hangzhou 310018, Zhejiang, Peoples R China
[2] Ryerson Univ, Dept Mech & Ind Engn, Toronto, ON, Canada
[3] Harbin Inst Technol, Sch Municipal & Environm Engn, Harbin, Heilongjiang, Peoples R China
[4] Hangzhou RUNPAQ Technol Co Ltd, Hangzhou, Zhejiang, Peoples R China
[5] Low Carbon Bldg Energy & Environm Engn & Technol, Hangzhou, Zhejiang, Peoples R China
基金
浙江省自然科学基金;
关键词
PERFORMANCE; MODEL;
D O I
10.1080/01457632.2019.1576423
中图分类号
O414.1 [热力学];
学科分类号
摘要
A hybrid ground-coupled heat pump (GCHP) is an efficient and sustainable technology for space heating and cooling. A demonstration house equipped with GCHP with a solar seasonal heat storage (SSHS) system had been built in Harbin, a severe cold zone of China. A dynamic simulation model was built for the house and GCHP with the SSHS system using TRNSYS. The model used a newly developed vertical ground heat exchanger (VGHE) module which considered coupled heat and moisture transfer (CHMT) in ground with variable soil properties (VSPs) and phase change of soil moisture (PCSM). In the simulation, a large amount of computing is consumed for VSP and PCSM, while the computing amount for moisture transfer is small. The model with the new VGHE module produced better simulated results, compared with the field data. So, CHMT-VSP-PCSM affects the performance of VGHE and system to some extent, especially CHMT. Hourly variation laws of temperatures and energy parameters were analyzed, and different characteristics were showed up at different operating stages in heating and cooling seasons for both long and short terms. The GCHP with the SSHS system can meet the heating and cooling demands of the house in general. In cooling season, adjusting the ratio of the two groups of VGHE for heat storage and cooling will increase the utilization efficiency of VGHE and make the soil temperature more balanced.
引用
收藏
页码:840 / 850
页数:11
相关论文
共 50 条
  • [41] The energy-saving effects of ground-coupled heat pump system integrated with borehole free cooling: A study in China
    Zhou, Zhihua
    Wu, Shengwei
    Du, Tao
    Chen, Guanyi
    Zhang, Zhiming
    Zuo, Jian
    He, Qing
    APPLIED ENERGY, 2016, 182 : 9 - 19
  • [42] Thermal characteristics of a seasonal solar assisted heat pump heating system with an underground tank
    Huang, Haotian
    Xiao, Yimin
    Lin, Jianquan
    Zhou, Tiecheng
    Liu, Yanan
    Zhao, Qian
    SUSTAINABLE CITIES AND SOCIETY, 2020, 53
  • [43] Estimation of soil and grout thermal properties for ground-coupled heat pump systems: Development and application
    Zhang, Linfeng
    Chen, Jiayu
    Wang, Junqi
    Huang, Gongsheng
    APPLIED THERMAL ENGINEERING, 2018, 143 : 112 - 122
  • [44] Operating characteristics of photovoltaic/thermal-ground source heat pump system in cold regions
    Wang, Fang
    Liu, Mengwei
    Pang, Dongqing
    Li, Zhiqiang
    Lu, Shixiang
    Du, Weifeng
    Guo, Wenliang
    Hu, Guangyu
    Yin, Jian
    APPLIED THERMAL ENGINEERING, 2024, 248
  • [45] A highly efficient solution for thermal compensation of ground-coupled heat pump systems and waste heat recovery of kitchen exhaust air
    Wang, Kuan
    Li, Nianping
    Peng, Jinqing
    Wang, Xiang
    Wang, Chunlei
    Wang, Meng
    ENERGY AND BUILDINGS, 2017, 138 : 499 - 513
  • [46] Simulation Tool for Ground-Source Heat Pump System with Multiple Ground Heat Exchangers
    Katsura, Tako
    Nagano, Katsunori
    ASHRAE TRANSACTIONS 2018, VOL 124, PT 2, 2018, 124 : 92 - 101
  • [47] Simulation study of solar-source heat pump system with sensible energy storage
    Bakirci, Kadir
    Yuksel, Bedri
    JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2021, 146 (04) : 1853 - 1864
  • [48] The design of a seasonal heat storage system with a geothermal heat pump for a residential building in Tehran
    Shamsabadi, Akbar Alidadi
    Jahangiri, Mehdi
    Rezaei, Tayebeh
    Farsani, Rouhollah Yadollahi
    Seryani, Ali
    Hakim, Siavash
    JOURNAL OF ENGINEERING DESIGN AND TECHNOLOGY, 2022, 20 (06) : 1606 - 1626
  • [49] Operation characteristics and experience of a ground source heat pump system with a vertical ground heat exchanger
    Michopoulos, A.
    Zachariadis, T.
    Kyriakis, N.
    ENERGY, 2013, 51 : 349 - 357
  • [50] ENHANCED GROUND SOURCE HEAT PUMP SYSTEM WITH THERMAL STORAGE SYSTEM
    Taira, Hirotoshi
    Sato, Takashi
    Kakizaki, Takao
    Oguma, Masahito
    PROCEEDINGS OF THE ASME 12TH INTERNATIONAL CONFERENCE ON ENERGY SUSTAINABILITY, 2018, 2018,