摘要
Moisture content is an important indicator of the insulation and arc extinguishing performance of SF6 insulated electrical equipment. The research shows that moisture measurements are strongly influenced by altitude pressures and the different order of pressure correction and temperature correction calculation, different calculation results will result. Therefore, in this paper, we studies the pressure and temperature environment based on moisture test of SF6 gas insulated equipment in power industry. Firstly, the PVT characteristics of pure SF6 gas and water vapor were analyzed and put forward the necessity of pressure correction, then combined the Pitzer-Veli equation of SF6 gas and Water Pitzer-Veli equation to fit PVT equation of state of SF6-H2O that suitable for electric power industry and deduced the Correction Formula of Moisture Measurement in SF6 Gas. Finally, through experiments, completion of the calibration formula optimization and verification SF6 electrical equipment on, proof of the applicability and effectiveness of the correction formula.
引用
收藏
页数:8
相关论文
共 28 条
  • [1] Research on SF6 Gas Monitoring Method in Power Equipment Based on Photoacoustic Spectroscopy
    Zhen Yan
    Wang Licheng
    Su Lan
    Bai Huifeng
    2019 IEEE 4TH INTERNATIONAL CONFERENCE ON CLOUD COMPUTING AND BIG DATA ANALYSIS (ICCCBDA), 2019, : 170 - 174
  • [2] Study of alternative test method of internal arcing by replacing SF6 with air in SF6-insulated power equipment
    Kotari M.
    Tadokoro T.
    Tanaka S.-I.
    Iwata M.
    IEEJ Transactions on Power and Energy, 2018, 138 (11): : 914 - 922
  • [3] The contact erosion characteristics of SF6 circuit breaker based on dynamic resistance measurement method
    Chen, Gong
    Li, Mengbo
    Wang, Qi
    Lu, Xiaojun
    Zhang, Sixiang
    Luo, Daijun
    ENERGY REPORTS, 2022, 8 : 1081 - 1089
  • [4] Study on SF6 Gas On-line Monitoring Method Based on Machine Learning
    Wang, Shijun
    Xia, Yi
    Ping, Chang
    Xue, Guobin
    PROCEEDINGS OF 2018 IEEE 4TH INFORMATION TECHNOLOGY AND MECHATRONICS ENGINEERING CONFERENCE (ITOEC 2018), 2018, : 240 - 244
  • [5] Recent Trend and Future Perspectives in Electrical Insulation Techniques in Relation to Sulfur Hexafluoride (SF6) Substitutes for High Voltage Electric Power Equipment
    Okubo, Hitoshi
    Beroual, Abderrahmane
    IEEE ELECTRICAL INSULATION MAGAZINE, 2011, 27 (02) : 34 - 42
  • [6] A novel method to evaluate insulation performance of SF6 alternative gases based on modified GIPF-Local properties model
    Hai, Bin
    Wang, Feng
    Zhong, Lipneng
    Chen, She
    Liang, Kaibin
    Tang, Nian
    Li, Li
    JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2025, 58 (03)
  • [7] Study on field demonstration of high sensitivity SF6 leakage detection method for gas insulated switchgear
    Tatemi M.
    Inami H.
    Rokunohe T.
    Hirose M.
    IEEJ Transactions on Power and Energy, 2020, 140 (05) : 409 - 414
  • [8] A Novel Diagnosis Method Based on the Feature Selection Algorithm and Convolutional Neural Network for SF6 Gas-Insulated Equipment
    Zhang, Haoyue
    Zeng, Fuping
    Lei, Zhicheng
    Cai, Rijian
    Li, Haotian
    Zhang, Shiling
    Tang, Ju
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2023, 30 (03) : 1274 - 1282
  • [9] Evaluation method of contact erosion for high voltage SF6 circuit breakers using dynamic contact resistance measurement
    Cheng, Tingting
    Gao, Wensheng
    Liu, Weidong
    Li, Ruipeng
    ELECTRIC POWER SYSTEMS RESEARCH, 2018, 163 : 725 - 732
  • [10] Nanomaterials-based gas sensors of SF6 decomposed species for evaluating the operation status of high-voltage insulation devices
    Cui, Hao
    Zhang, Xiaoxing
    Zhang, Jun
    Zhang, Ying
    HIGH VOLTAGE, 2019, 4 (04) : 242 - 258