Testing, simulation and soft-optimization of R410A low-GWP alternatives in heat pump system

被引:58
作者
Alabdulkarem, Abdullah [1 ]
Eldeeb, Radia [2 ]
Hwang, Yunho [2 ]
Aute, Vikrant [2 ]
Radermacher, Reinhard [2 ]
机构
[1] King Saud Univ, Dept Mech Engn, Riyadh 11421, Saudi Arabia
[2] Univ Maryland, Ctr Environm Energy Engn, Dept Mech Engn, College Pk, MD 20742 USA
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2015年 / 60卷
关键词
R410A; Heat pumps; AREP; Alternative lower GWP refrigerants; Compressor size; Suction line heat exchanger; PERFORMANCE; FLOW; EXCHANGER;
D O I
10.1016/j.ijrefrig.2015.08.001
中图分类号
O414.1 [热力学];
学科分类号
摘要
The environmental impact of high global warming potential (GWP) refrigerants pushed the HVAC&R industry to investigate alternative refrigerants. R410A is a common refrigerant for air conditioning and heat pumping applications, but has a GWP of 2088. Drop-in tests of three R410A low-GWP alternative refrigerants (R32, D2Y60 and L41a) in a 10.55 kW capacity split heat pump unit were performed. The results show that R32 and L41a are good replacement candidates for R410A. A finite volume heat exchanger model and component based vapor compression system simulation tools were validated against the experimental data. Most of the predicted COP and capacity results of R32 experiments lie within 5% of the measured values, which is in good agreement with the experiments. Further investigation was carried out by varying the size of the compressor and adding a suction line heat exchanger to the system to match the capacity to that of R410A. (C) 2015 Elsevier Ltd and International Institute of Refrigeration. All rights reserved.
引用
收藏
页码:106 / 117
页数:12
相关论文
共 29 条
  • [1] Alefeld G., 1993, HEAT CONVERSION SYST
  • [2] [Anonymous], 2021, CLIM CHANG 2021 SYNT
  • [3] ANSI/ASHRAE, 2010, 116 ANSIASHRAE
  • [4] *ARI, 2008, 210240 ARI
  • [5] Bhatti M.S., 1987, HDB SINGLE PHASE HEA
  • [6] Condensation inside and outside smooth and enhanced tubes - a review of recent research
    Cavallini, A
    Censi, G
    Del Col, D
    Doretti, L
    Longo, GA
    Rossetto, L
    Zilio, C
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2003, 26 (04): : 373 - 392
  • [7] Performance of a new refrigeration cycle using refrigerant mixture R32/R134a for residential air-conditioner applications
    Chen, Jianyong
    Yu, Jianlin
    [J]. ENERGY AND BUILDINGS, 2008, 40 (11) : 2022 - 2027
  • [8] CHURCHILL SW, 1977, CHEM ENG-NEW YORK, V84, P91
  • [9] Dittus F.W., 1985, Int. Commun. Heat Mass, V12, P3, DOI [10.1016/0735-1933(85)90003-X, DOI 10.1016/0735-1933(85)90003-X]