Evaluation of an "Off the Shelf" automated chemical phosphorus removal system

被引:3
作者
Craig, K. [1 ]
Minnema, R. [2 ]
Dabkowski, B. [1 ]
Gironi, M. S. [1 ]
机构
[1] Hach Lange Co, Loveland, CO 80538 USA
[2] City Beaver Dam, Beaver, WI USA
来源
12TH INTERNATIONAL CONFERENCE ON COMPUTING AND CONTROL FOR THE WATER INDUSTRY, CCWI2013 | 2014年 / 70卷
关键词
Instrumentation; Automation; Chemical Phosphorus Removal; Analyzer; Real Time Control;
D O I
10.1016/j.proeng.2014.02.041
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In order to reduce ferric chloride consumption and maintain effluent compliance, the wastewater plan in Beaver Dam, Wisconsin installed an 'off the shelf' phosphorus control system manufactured by Hach Lange Company. In this installation, the phosphorus control system measures effluent orthophosphate and flow, using that information in the algorithms to control ferric chloride feed in real time before the final clarifiers. After 160 days of operation, the phosphorus control system reduced the ferric chloride feed by 56% (26,688 gallons) which equates to approximately $30, 691 saved in chemical costs alone. Based upon these figures, return on investment of the installed cost of the phosphorus control system was 6.8 months. (C) 2013 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:363 / 368
页数:6
相关论文
共 3 条
[1]  
Schulyer R., 2005, ACTIVATED SLUDGE PRO
[2]  
Water Environment Federation, 2005, BIOL NUTR REM BNR OP
[3]  
Water Environment Federation, 2007, WEF NUTR REM C BALT