Thermal Management of Time-Varying High Heat Flux Electronic Devices

被引:24
作者
David, T. [1 ]
Mendler, D. [1 ]
Mosyak, A. [1 ]
Bar-Cohen, A. [2 ]
Hetsroni, G. [1 ]
机构
[1] Technion Israel Inst Technol, Dept Mech Engn, IL-32000 Haifa, Israel
[2] Univ Maryland, Dept Mech Engn, College Pk, MD 20742 USA
关键词
pin-fin microchannel; varying high heat flux; chip cooling; infrared; PARALLEL MICROCHANNELS; BOILING INSTABILITY; PRESSURE-DROP; 2-PHASE FLOW; SINKS; VISUALIZATION;
D O I
10.1115/1.4027325
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The thermal characteristics of a laboratory pin-fin microchannel heat sink were empirically obtained for heat flux, q '', in the range of 30-170 W/cm(2), mass flux, m, in the range of 230-380 kg/m(2) s, and an exit vapor quality, x(out), from 0.2 to 0.75. Refrigerant R 134a (HFC-134a) was chosen as the working fluid. The heat sink was a pin-fin microchannel module installed in open flow loop. Deviation from the measured average temperatures was 1.5 degrees C at q = 30 W/cm(2), and 2.0 degrees C at q = 170 W/cm(2). These results indicate that use of pin-fin microchannel heat sink enables keeping an electronic device near uniform temperature under steady state and transient conditions. The heat transfer coefficient varied significantly with refrigerant quality and showed a peak at an exit vapor quality of 0.55 in all the experiments. At relatively low heat fluxes and vapor qualities, the heat transfer coefficient increased with vapor quality. At high heat fluxes and vapor qualities, the heat transfer coefficient decreased with vapor quality. A noteworthy feature of the present data is the larger magnitude of the transient heat transfer coefficients compared to values obtained under steady state conditions. The results of transient boiling were compared with those for steady state conditions. In contrast to the more common techniques, the low cost technique, based on open flow loop was developed to promote cooling using micropin fin sinks. Results of this experimental study may be used for designing the cooling high power laser and rocket-born electronic devices.
引用
收藏
页数:10
相关论文
共 41 条
[1]  
Agostini B, 2008, INT J HEAT MASS TRAN, V51, P5400, DOI 10.1016/j.ijheatmasstransfer.2008.03.006
[2]  
[Anonymous], 1995, GUID EXPR UNC MEAS
[3]  
[Anonymous], 2004, THERM PROP HFC 134A
[4]   On the nature of critical heat flux in microchannels [J].
Bergles, AE ;
Kandlikar, SG .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 2005, 127 (01) :101-107
[5]   Refrigerant flow boiling heat transfer in parallel microchannels as a function of local vapor quality [J].
Bertsch, Stefan S. ;
Groll, Eckhard A. ;
Garimella, Suresh V. .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2008, 51 (19-20) :4775-4787
[6]   Two-phase flow instabilities in a silicon microchannels heat sink [J].
Bogojevic, D. ;
Sefiane, K. ;
Walton, A. J. ;
Lin, H. ;
Cummins, G. .
INTERNATIONAL JOURNAL OF HEAT AND FLUID FLOW, 2009, 30 (05) :854-867
[7]  
Bohr MT, 1995, INTERNATIONAL ELECTRON DEVICES MEETING, 1995 - IEDM TECHNICAL DIGEST, P241, DOI 10.1109/IEDM.1995.499187
[8]   Experimental study of unsteady convective boiling in heated minichannels [J].
Brutin, D ;
Topin, F ;
Tadrist, L .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2003, 46 (16) :2957-2965
[9]   Experimental investigation of transient boiling heat transfer in microchannels [J].
Diaz, M. Cortina ;
Schmidt, J. .
INTERNATIONAL JOURNAL OF HEAT AND FLUID FLOW, 2007, 28 (01) :95-102
[10]  
Hetsrom G., 2000, ASME INT MECH ENG C