Effects of Cross Level Air Interaction within Multilevel Underground Carparks on Indoor Air Quality

被引:7
作者
Al-Waked, Rafat [1 ]
Yassin, Abdalrahman [1 ]
Adwan, Abdallah [1 ]
Mostafa, Diala Bani [1 ]
机构
[1] German Jordanian Univ, Dept Mech & Maintenance Engn, Amman 11180, Jordan
关键词
CFD; hybrid cars; electrical cars; carpark; ventilation; carbon monoxide; IAQ; GREENHOUSE-GAS EMISSIONS; HYBRID ELECTRIC VEHICLES; CARBON-MONOXIDE; VENTILATION SYSTEM; TRANSPORT; EXPOSURE; POLLUTANTS; PARKS; CO2;
D O I
10.3390/fluids5040177
中图分类号
O3 [力学];
学科分类号
08 ; 0801 ;
摘要
Ventilation for underground carparks is critical to indoor air quality (IAQ) due to carbon monoxide (CO) emissions from cars. The IAQ within a multi-level underground carpark of a shopping mall has been investigated using computational fluid dynamics (CFD) model based on ANSYS-FLUENT (18.1) software. The effects of car engines types, porosity of supply and exhaust air louvers and ventilation flow rates on IAQ were examined. A mesh sensitivity study was conducted and the CFD model was validated against the fully mixed mathematical formulations of IAQ with a maximum difference in values of 1.5 ppm and an error of 3.4%. The results showed that the ventilation system must be operated at ACH value of more than 2.7 in order to meet the required CO concentration of 50 ppm within the carpark and should be based on running cars within each level rather than the parking capacity of each level. Porosity of louvers affected air flow distribution between parking levels and led to higher dilution of CO. Therefore, modelling a multilevel underground carpark requires closer attention to cross level interaction across Ramps which could affect the CO concentration within a given level.
引用
收藏
页数:22
相关论文
共 51 条
[1]   Study of Securing Required Ventilation Rates and Improving Mechanical Ventilation Systems for Underground Parking Lots [J].
Ahn, Se-Jin ;
Kwon, Hyuk-Min ;
Kim, Geum-Hee ;
Yang, Jeong-Hoon .
JOURNAL OF ASIAN ARCHITECTURE AND BUILDING ENGINEERING, 2016, 15 (03) :659-665
[2]  
AIRAH, 2018, IND AIR QUAL HDB, P133
[3]  
Al-Waked R., 2017, Univers. J. Mech. Eng., V5, P113, DOI [10.13189/ujme.2017.050402, DOI 10.13189/UJME.2017.050402]
[4]  
[Anonymous], 2013, ANSI/ASHRAE Standard 62.1-2013:, Vent. Accept. Indoor Air Qual
[5]  
ANSYS, 2017, ANS 18 ANS FLUENT US
[6]  
ASHRAE, 2019, 2019 ASHRAE HDB HEAT
[7]  
Boureima Faycal-Siddikou., 2009, World Electric Vehicle Journal, P469, DOI [10.3390/wevj3030469, DOI 10.3390/WEVJ3030469]
[8]  
British Standards Institution, 2013, 734672013 BS
[9]   Criteria for air quality in enclosed car parks [J].
Burnett, J ;
Chan, MY .
PROCEEDINGS OF THE INSTITUTION OF CIVIL ENGINEERS-TRANSPORT, 1997, 123 (02) :102-110
[10]   Exposure to carbon monoxide in enclosed multi-level parking garages in the central Athens urban area [J].
Chaloulakou, A ;
Duci, A ;
Spyrellis, N .
INDOOR AND BUILT ENVIRONMENT, 2002, 11 (04) :191-201