Induced voltage at two poles of 10kV parallel distribution line caused by direct lightning strike on the phase wire of adjacent line

被引:4
作者
Zhao, Yating [1 ]
Wang, Jianguo [1 ]
Cai, Li [1 ]
Li, Quanxin [1 ]
Zhou, Mi [1 ]
Su, Rui [1 ]
Xu, Zhiling [1 ]
Fan, Yadong [1 ]
机构
[1] Wuhan Univ, Sch Elect Engn & Automat, Wuhan 430072, Peoples R China
关键词
Induced voltage; Direct lightning; Rocket -triggered lightning; Distribution line; POWER DISTRIBUTION LINES; SURGE ARRESTERS; PART I; PERFORMANCE; STROKES; SYSTEM;
D O I
10.1016/j.epsr.2022.108215
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Triggered lightning was used to strike different phase wires of a 10 kV double circuit distribution line in 2018. The induced voltage on two poles of the other circuit is analyzed. When it struck on phase A, for the pole close to the strike point, the induced voltage of the lowest phase C is different from that of the two phases, with three obvious negative pulses and one prominent positive pulse. The negative peak of three-phase overvoltage ranges from -11.7 kV to -65.2 kV corresponding to lightning current from -8.3 kA to -18.1 kA. For the three-phase voltage on the pole far away from the strike point, its negative peak is between -10.5 kV and -42.8 kV corresponding to lightning current from -8.3 kA to -26.7 kA. The test method and results proposed in this paper will be helpful to the research on the lightning overvoltage response of parallel power distribution lines.
引用
收藏
页数:9
相关论文
共 29 条
[1]   Utilization of Underbuilt Shield Wires to Improve the Lightning Performance of Overhead Distribution Lines Hit by Direct Strokes [J].
Araneo, Rodolfo ;
Andreotti, Amedeo ;
Brandao Faria, Jose ;
Celozzi, Salvatore ;
Assante, Dario ;
Verolino, Luigi .
IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (04) :1656-1666
[2]   Induced voltage measurements on an experimental distribution line during nearby rocket triggered lightning flashes [J].
Barker, PP ;
Short, TA ;
EybertBerard, AR ;
Berlandis, JP .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (02) :980-995
[3]  
Belko D. O., 2016, 2016 33 INT C LIGHTN, P1
[4]   Observation of Natural Lightning-Induced Voltage on Overhead Power Lines [J].
Cai, Li ;
Wang, Jianguo ;
Zhou, Mi ;
Chen, Shaodong ;
Xue, Jian .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (04) :2350-2359
[5]   Lightning-Induced Voltages on a Distribution Line With Surge Arresters Using a Hybrid FDTD-SPICE Method [J].
Chen, Hongcai ;
Du, Yaping ;
Yuan, Mengqing ;
Liu, Qing Huo .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (05) :2354-2363
[6]   Distribution of currents in the lightning protective system of a residential building - Part I: Triggered-lightning experiments [J].
DeCarlo, Brian A. ;
Rakov, Vladimir A. ;
Jerauld, Jason E. ;
Schnetzer, George H. ;
Schoene, Jens ;
Uman, Martin A. ;
Rambo, Keith J. ;
Kodali, Venkateswararao ;
Jordan, Douglas M. ;
Maxwell, Guy ;
Humeniuk, Stephen ;
Morgan, Mark .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) :2439-2446
[7]   DISCUSSION ABOUT THE INDUCING EFFECTS OF LIGHTNING IN AN EXPERIMENTAL POWER DISTRIBUTION LINE IN MEXICO [J].
DELAROSA, F ;
VALDIVIA, R ;
PEREZ, H ;
LOZA, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (03) :1080-1089
[8]   LIGHTNING PERFORMANCE AND OVERVOLTAGE SURGE STUDIES ON A RURAL DISTRIBUTION LINE [J].
ERIKSSON, AJ ;
MEAL, DV .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1982, 129 (02) :59-69
[9]   Performance of MOV arresters during very close, direct lightning strikes to a power distribution system [J].
Fernandez, MI ;
Rambo, KJ ;
Rakov, VA ;
Uman, MA .
IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (02) :411-418
[10]  
Imai Y., 2010, ELECTR ENG JPN, V111, P72