How does a change in the control room design affect diagnostic strategies in nuclear power plants?

被引:7
作者
Kim, Dong Young [1 ,2 ]
Kim, Jonghyun [1 ]
机构
[1] KEPCO Int Nucl Grad Sch, Ulsan 689882, South Korea
[2] Korea Hydro & Nucl Power Co, Human Resources Dev Inst, Ulsan 689882, South Korea
关键词
main control room; diagnosis; operation; INFORMATION; PERFORMANCE; KNOWLEDGE; BEHAVIOR; SYSTEM;
D O I
10.1080/00223131.2014.923792
中图分类号
TL [原子能技术]; O571 [原子核物理学];
学科分类号
0827 ; 082701 ;
摘要
Recently, main control rooms have been considerably changed by modern computer techniques. Some of the features that distinguish digital control rooms from conventional, analog rooms in nuclear power plants include advanced alarm systems, graphic information display systems, computerized procedure systems, and soft control. These features can bring changes in operator tasks, changing the characteristics of tasks or creating new tasks for operators. It is especially expected that these features may bring out changes in the operator's diagnostic tasks and strategies in a digital control room as compared with an analog control room. This study investigates the differences in the operator's diagnostic tasks and strategies in analog and digital control rooms. This study also attempts to evaluate how new systems in a digital control room affect diagnostic strategies. Three different approaches, which are complementary, are used to identify diagnostic strategies in the digital control room and in the analog control room: (1) observation in the simulator, (2) interview with operators, and (3) a literature review. The results show that the digital control room introduces new diagnosis strategies compared with the analog control room while also changing the characteristics of the strategies, mostly by gaining more support from the computerized system.
引用
收藏
页码:1288 / 1310
页数:23
相关论文
共 26 条
[1]  
[Anonymous], NUREGCR6634 US NRC
[2]   The change in concepts needed to account for human behavior in complier dynamic tasks [J].
Bainbridge, L .
IEEE TRANSACTIONS ON SYSTEMS MAN AND CYBERNETICS PART A-SYSTEMS AND HUMANS, 1997, 27 (03) :351-359
[3]  
Brown W, 2004, DEV DETAILED HUMAN F
[4]  
Choi HS, 2012, T KOR NUCL SOC OCT 2
[5]  
KHNP (Korea Hydro & Nuclear Power Company), 1994, YGN 3 4 FIN SAF AN R
[6]  
KHNP (Korea Hydro & Nuclear Power Company), 2001, APR1400 STAND SAF AN
[7]   COMPUTERIZED SYSTEMS FOR ONLINE MANAGEMENT OF FAILURES - A STATE-OF-THE-ART DISCUSSION OF ALARM SYSTEMS AND DIAGNOSTIC SYSTEMS APPLIED IN THE NUCLEAR INDUSTRY [J].
KIM, IS .
RELIABILITY ENGINEERING & SYSTEM SAFETY, 1994, 44 (03) :279-295
[8]  
Kim J., 2002, Journal of the Korea Nuclear Society, V33, P301
[9]   Investigation on applicability of information theory to prediction of operator performance in diagnosis tasks at nuclear power plants [J].
Kim, JH ;
Lee, SJ ;
Seong, PH .
IEEE TRANSACTIONS ON NUCLEAR SCIENCE, 2003, 50 (04) :1238-1252
[10]  
Kim JH, 2011, ICI2011 AUG 21 25 DA