A Novel Distance Protection Algorithm for the Phase-Ground Fault

被引:36
作者
Zhong, Ying [1 ]
Kang, Xiaoning [1 ]
Jiao, Zaibin [1 ]
Wang, Zengchao [2 ]
Suonan, Jiale [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, Xian 710049, Shaanxi, Peoples R China
[2] Elect Power Dispatching & Control Ctr Guangdong P, Guangzhou 510000, Guangdong, Peoples R China
基金
中国国家自然科学基金;
关键词
Calculated fault distance; distance protection algorithm; linear differential equation; lumped transmission-line model; overreach; COMPENSATION; IMPEDANCE; RELAY;
D O I
10.1109/TPWRD.2013.2286627
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Traditional distance relays often mis-operate for high transient resistance in phase-ground faults by measuring apparent impedance. To solve this problem, a novel distance protection algorithm is proposed in this paper. It is deduced in the RL lumped transmission line model and calculates the fault distance from the measuring point to the fault point by solving a linear differential equation. In addition, a protection criteria based on the comparison result between the calculated fault distance and the protective setting margin rather than the protective zone measured by apparent impedance is set up in this paper. As a result, the proposed method can avoid overreach for the given characteristics that the calculated fault distance is greater than the actual fault distance when the fault occurs next to the opposite terminal. Meanwhile, both the fundamental component and one decaying DC component are needed to solve the differential equation for the proposed distance algorithm, therefore it can trip the breaker fast during the fault transient period. Finally, EMTP simulation results verify the validity of the proposed distance algorithm on RL transmission line model. However, to put the proposed method into field use, the problem caused by the distributed capacitance of the transmission line on the proposed method will be further studied and solved.
引用
收藏
页码:1718 / 1725
页数:8
相关论文
共 14 条
[1]   A SIMPLIFIED ALGORITHM FOR DIGITAL DISTANCE PROTECTION BASED ON FOURIER TECHNIQUES [J].
DAMORE, D ;
FERRERO, A .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (01) :157-164
[2]   Ground distance relay compensation based on fault resistance calculation [J].
Eissa, M. M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (04) :1830-1835
[3]   Ground distance relaying with fault-resistance compensation for unbalanced systems [J].
Filomena, Andre Daros ;
Salim, Rodrigo Hartstein ;
Resener, Mariana ;
Bretas, Arturo Suman .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (03) :1319-1326
[4]  
Horowitz S.H., 2008, POWER SYSTEM RELAYIN, P23
[5]   Adaptive impedance relay with composite polarizing voltage against fault resistance [J].
Liu, Q. K. ;
Huang, S. F. ;
Liu, H. Z. ;
Liu, W. S. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (02) :586-592
[6]   A New Digital Distance Relaying Scheme for Compensation of High-Resistance Faults on Transmission Line [J].
Makwana, Vijay H. ;
Bhalja, Bhavesh R. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (04) :2133-2140
[7]   DIGITAL CALCULATION OF IMPEDANCE FOR TRANSMISSION LINE PROTECTION [J].
MANN, BJ ;
MORRISON, IF .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1971, PA90 (01) :270-&
[8]  
Ricardo M. S., 2012, APPL SCI, V2
[9]   NEW ALGORITHM FOR DIGITAL IMPEDANCE RELAYS [J].
SACHDEV, MS ;
BARIBEAU, MA .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1979, 98 (06) :2232-2240
[10]  
Suonan J. L., 2006, J XIAN JIAOTONG U, V40, P68