Traceability of Low-Power Voltage Transformer for Medium Voltage Application

被引:17
作者
Pasini, Gaetano [1 ]
Peretto, Lorenzo [1 ]
Roccato, Paolo [2 ]
Sardi, Angelo [2 ]
Tinarelli, Roberto [1 ]
机构
[1] Univ Bologna, Dept Elect Elect & Informat Engn Guglielmo Marcon, I-40136 Bologna, Italy
[2] Ist Nazl Ric Metrol, High Voltage High Power Test & Calibrat Lab, I-10135 Turin, Italy
关键词
Calibration; instrument transformer (IT); traceability; uncertainty; voltage transformer (VT); INSTRUMENT TRANSFORMERS; CALIBRATION;
D O I
10.1109/TIM.2014.2318373
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, the measuring and calibration techniques useful for ensuring the traceability of nonconventional voltage transformer (VT), used in ac power plant up to 52 kV, are described and discussed. In particular, a setup made by commercially available devices is presented and an in-depth accuracy analysis is performed by considering all the uncertainty sources located in the measurement chain. The obtained results prove that it can be used for the calibration of 0.5 accuracy class low-power VTs. In addition, the sources that contribute more to the uncertainties on the ratio and phase errors are highlighted and suggestions on where to act to further improve the accuracy of the presented setup are given.
引用
收藏
页码:2804 / 2812
页数:9
相关论文
共 19 条
[1]  
[Anonymous], 2013, 61869 IEC
[2]  
[Anonymous], 2012, 600447 IEC
[3]  
[Anonymous], 2011, 60201104 ISOIEC
[4]  
[Anonymous], 2003, 600442 IEC
[5]  
[Anonymous], 2008, EV MEAS DAT S1
[6]  
[Anonymous], 2014, WHAT IS EFFECTIVE NU
[7]  
[Anonymous], 1998, 142531 EN
[8]  
[Anonymous], 1995, 1002008 JCGM GUM
[9]   A Simple Method for the Calibration of Traditional and Electronic Measurement Current and Voltage Transformers [J].
Brandolini, Arnaldo ;
Faifer, Marco ;
Ottoboni, Roberto .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2009, 58 (05) :1345-1353
[10]  
Crotti G., P 2012 CPEM WASH DC, P558